Radiators

Installed radiators

At 24 Dec 2023.

Room Inlet TRV


Dining area R L


Lounge R L


Back room R R


Bathroom R L


Study




Hall R R


Front bedroom L R


Back bedroom R L



Flow temperature

Return temperature

According to BSRIA, BS EN 14511 (the standard used for testing heat pumps) specifies a flow temperature of 45°C and a return temperature of 40°C, i.e. a temperature drop across radiators of 5°C.

Octopus say they are sizing radiators using a "flow temperature" of 45°C. By studying the correction factors they are using (see beginning of the Radiators section below) they appear to be using a radiator temperature of 42°C. So they are presumably assuming a return temperature of 39°C, and a drop across the radiators of 6°C.


There seems to be a rule-of-thumb to use a drop through the radiators of 1/7 of the flow temperature, i.e. 7°C for 50°C flow and 8°C for 55°C. The government Report on compliance on page 63 uses 1/7 (quoting the original MCS Heat Emitter Guide), and Octopus's use of 6°C for 45°C flow and the general use of 10°C with 70°C flow are consistent with this. Hopefully this will not affect radiator sizes too much.

This rule-of-thumb doesn't make much sense to me. It would make more sense to use a fraction of the difference between the flow temperature and room temperature. The following table shows this fraction for various examples, assuming a room temperature of 20°C:

Flow temperature Return temperature Drop across radiators ΔT Fraction
45 40 5 25 0.2
45 39 6 25 0.24
70 60 10 50 0.2

Hello Renewables aim for a 50/55°C flow temperature. This would suggest drop of 10/11°C across the radiators and an average radiator temperature of 45/49.5°C. So using an average radiator temperature of 47°C for sizing radiators would be consistent with this aim.

SCOP dependence on flow temperature

The MCS certified products directory provides SCOP values for heat pumps at different flow temperatures. These values are lower than those in the Daikin product catalogue, so they are presumably for different conditions.

The MCS certification for the Daikin EDLQ07CAV3 Monobloc (as used by Octopus) lists a SCOP of 3.57 at a flow temperature of 45°C.

The MCS certification for the Daikin ERGA06EVA heat pump provides the following table of SCOP values at different flow temperatures:

Flow temperature °C SCOP
45 3.7
46 3.64
47 3.59
48 3.54
49 3.48
50 3.43
51 3.37
52 3.32
53 3.26
54 3.21
55 3.15

Using the Altherma M at a flow temperature of 45°C (as specified by Octopus) would produce a SCOP of 3.57.

Using the Altherma 3 R at a flow temperature of 50°C would produce a SCOP of 3.43 (0.14 less than Octopus)
Using the Altherma 3 R at a flow temperature of 55°C would produce a SCOP of 3.15 (0.42 less than Octopus).

Hello Renewables aim for a 50/55°C flow temperature. According to my flow temperature notes above, this would suggest drop of 10/11°C across the radiators and an average radiator temperature of 45/49.5°C. So using a flow temperature of 52°C and an average radiator temperature of 47°C for sizing radiators would be consistent with this aim.

If we assume a 6°C drop through the radiators, the average radiator temperature will be 47/52°C for a flow temperature of 50/55°C.

Derating

Updated Sep 2023 to use later Stelrad table (slightly smaller factors) and add extra entries.

According to Stelrad a radiator specified at ΔT 50°C has to be derated by the factors in this table:

ΔT °C Operating factor
20 0.302
21 0.322
22 0.342
23 0.363
24 0.383
25 0.404
26 0.426
27 0.447
28 0.469
29 0.491
30 0.513
31 0.535
32 0.558
33 0.581
34 0.604
35 0.626
36 0.651
37 0.675
38 0.699
39 0.723
40 0.747

Available radiators

Stelrad radiator types

Type Description Power density W/m² Space between radiator and wall mm Projection from wall mm Pipe centres from wall mm Water contents l/m²
K1 Single panel, one set of fins 1700 19 / 30 83 / 94 51 / 62 5.5
P+ Double panel, one set of fins 2460 23 / 34 101 / 112 62 / 73 11
K2 Double panel, two sets of fins 3130 22 / 33 124 / 135 73 / 84 11
K3 Triple panel, three sets of fins 3980 22 180 73

Where two figures are given for distances from the wall these correspond to two possible orientations of the mounting brackets.

Water contents figures are approximate. See table in this Stelrad document for more accurate figures, broken down by radiator height.

Stelrad radiator weights

Weights in kg/m. I.e. multiply by radiator width to get radiator weight. Data from Stelrad Compact Horizontal and Compact K3 documents.


450mm height 600mm height 700mm height 1800mm heght
K1 14.51 19.70 22.90
P+ 22.04 29.80 34.50
K2 25.90 35.00 40.53 88.8
K3  43.40 (500mm height) 52.50 60.77

If the maximum radiator weight I can handle is 35kg, then the following table gives the maximum usable widths and corresponding powers:


450mm height 600mm height 700mm height 1800mm height
K1 2400mm
1814W
1800mm
1764W
1500mm
1563W

P+ 1500mm
1478W
1100mm
1481W
1000mm
1532W

K2 1300mm
1645W
1000mm
1732W
800mm
1568W
400mm
1584W
K3  800mm (500mm height)
1645W
600mm
1433W
500mm
1356W

Stelrad radiators

Stelrad vertical radiators (Stelrad prices)
Range Type Size mm Power W Price £ inc VAT
Classic Compact Vertical K2 1800 x 400 1584 308
Classic Compact Vertical K2 1800 x 500 1980 339
Classic Compact Vertical K2 1800 x 600 2376 371


Stelrad Classic Compact radiators (Stelrad prices)
Type Size mm Power W Price £ inc VAT
P+ 600 x 400 539 60
K2 600 x 400 693 71
K2 700 x 400 784 98
K2 450 x 600 822 89
K2 600 x 700 1212 100
K2 450 x 900 1234 105
K2 600 x 800 1385 118
K2 700 x 700 1372 137
K2 600 x 900 1558 115
K2 700 x 800 1568 145
K2 450 x 1200 1645 135
K2 450 x 1000 1371 112
K2 600 x 1000 1732 122
K2 700 x  900 1764 157
P+ 700 x 1200 1839 184
P+ 600 x 1400 1885 167
K2 600 x 1100 1905 135
K2 450 x 1400 1919 173
K2 700 x 1000 1960 167
K2 600 x 1200 2078 147
K3 600 x 900 2150 212
K2 700 x 1100 2156 184

Kudox radiators

See Kudox Technical Data and Fitted Dimensions.

Type Description Power density W/m² Space between radiator and wall mm Projection from wall mm Pipe centres from wall mm
T11 Single panel, one set of fins 1700 20 85 50
T21 Double panel, one set of fins 2460 31 101 66
T22 Double panel, two sets of fins 3130 31 135 83
T33 Triple panel, three sets of fins 3980 31 191 83

Compression fittings

Some measurements for 15mm pipe and compression fittings:

Pipe clip: pipe centre to wall: 19mm
Pipe clip: total projection from wall: 27mm
Pipe insertion depth: 14mm
Pipe insertion depth to face of untightened nut): 22mm
Elbow: overall size: 45mm
Elbow: pipe centre to face of other nut (untightened): 30mm
Pair of elbows: minimum distance between pipe centres: 60mm
Pair of elbows: pipe length for minimum distance between pipe centres: 44mm
Elbow: pipe end to centre of other pipe: 7mm
Elbow: projection of pipe from wall to join pipe clipped to wall: 19-7 = 12mm

The measurement for elbows also appy to tees and radiator valves.

Radiator pipe centres are approximately 25mm above the bottom of the radiator.

If we have a pipe clipped to a wall, and use two elbows to move the pipe away from the wall, the moved pipe centre will be at least 19+60 = 79mm away from the wall.

If this two-elbow method is used to connect to a K2 radiator, the radiator support brackets must be used to provide pipe centres 84mm from the wall. Note that with the brackets this way round, there will be 33mm space between the radiator and the wall - not enough to fit an elbow in. The radiator pipe centres would need to be at least 3x30 = 90mm above the horizontal wall pipe centres (30mm for each elbow, and 30mm for the valve bend).

The two-elbow method can't be used to connect to a P+ radiator, since the radiator support brackets can only provide pipe centres 62mm or 73mm from the wall. In this case, the radiator valves could be angled so that the pipes below them go back to elbows on the horizontal pipes clipped to the wall. The angle would need to handle an offset of 62-19 = 43mm. To keep the angle reasonable, the vertical distance between the radiator pipe centre and the horizontal pipe centre should be at least double this offset, i.e. at least 86mm. This would put the bottom of the radiator at least 86-25 = 61mm above the horizontal pipe centre.

If we wanted to use the angle method with a K2 radiator, the offset would be 73-19 = 54mm and the vertical distance would need to be at least 108mm, putting the bottom of the radiator at least 108-25 = 83mm above the horizontal pipe centre.

Heat losses

Updated Oct 2024:.

This table shows the heat losses at various outdoor temperatures according to my latest heat model (lossSL.yaml).

The ensuite and study doors are assumed to be open (assumed closed before Aug 2024).
All setpoints are assumed to be 21°C, except for the lounge entrance at 21.6 (MCS setpoints assumed before Aug 2024).

Heat losses for various outdoor temperatures
Room -10°C -7°C -5°C -2°C 0°C 2°C 7°C 10°C 15°C
Lounge entrance
11581085
Lounge corner
506437
Dining room
676596
Back room
876788
Front bedroom
646569
Back bedroom
527464
Hall
764676
Study
723655
Bathroom
284255
Ensuite
234207
Total

63935732

Total heat loss varies by 210W/°C for outside temperatures in range -5°C to 10°C, and can be approximated by 5053-210*T, where T is outside temperature.

We currently don't have a radiator in the ensuite (apart from the towel radiator), but we could install one. To handle the 200W heat loss at -2°C with a radiator temperature of 48°C and a room temperature of 21°C, we would need a radiator rated at 200/0.447 = 447W. A K1 450x600 radiator is rated at 454W.
Simon on 12 Sep 2024 calculated the ensuite loss at 300W, for which we would need a radiator rated at 300/0.447 = 671W. This would require a K1 600x700 @ 686W, or one of our spare P+ 600x600 @ 808W, or a K2 450x500 @ 685W.

To handle the 633W loss in the study at a radiator temperure of 48°C would require a radiator rated at 633/.447 = 1416W. The most powerful radiator we could install in the available width is a K3 600x400 rated at 956W. This would require a derating of at most 633/956 = 0.662, which corresponds to a ΔT of 36°C and hence a radiator temperature of 21+36 = 57°C.

Insulating both the ceiling and the garage wall of the study could reduce the loss to about 452W. With a K3 600x400 this would require a derating of at most 452/956 = 0.473, which corresponds to a ΔT of 28°C and hence a radiator temperature of 21+28 = 49°C.

Comparison of possible radiator changes

Written Sep 2024

This section compares the possible radiator changes investigated in the following sections. The possibilities are:

Plan Q adds a radiator in the back room to the existing set (minimum requirement for Octopus 2024).
Plan R is like plan Q but with a larger hall radiator.
Plan SL is like plan R but with an extra radiator in the lounge, and not such a big hall radiator.

Red cells indicate rooms where the temperature is more than 0.2°C below the target temperature (i.e. 20.7°C or less).

This table shows room temperatures with a radiator temperature of 48°C (flow temperature 50°C) and outside temperature of -2°C.

RoomPlan SLPlan RPlan Q
Lounge entrance21.4

Lounge20.820.620.0
Lounge corner21.0

Dining room21.020.920.3
Back room21.021.021.0
Hall20.621.018.6
Study19.119.317.6
Front bedroom20.820.520.0
Back bedroom20.820.520.1
Ensuite19.619.418.9
Bathroom21.021.021.0
Kitchen18.117.817.1

This table shows room temperatures with a radiator temperature of 52°C (flow temperature 55°C) and outside temperature of -5°C.

RoomPlan SLPlan RPlan Q
Lounge entrance21.7

Lounge20.920.820.5
Lounge corner21.0

Dining room21.021.020.9
Back room21.021.021.0
Hall21.021.018.9
Study19.319.317.8
Front bedroom21.020.820.4
Back bedroom21.020.820.5
Ensuite19.719.519.2
Bathroom21.021.021.0
Kitchen18.017.617.1

Radiator for lounge corner

The current radiators have a combined rated power of 3944W, which provides 

The original Octopus specification had a heat loss of 1993W, which requires rated power of 6151W at a flow temperature of 45°C. 

Possible radiators to go in corner of lounge to left of fireplace:

RadiatorTypeCountryColourRated power WWidth mmHeight mmPrice £Comments
Monster ShopFlat panel. DoubleWithheldWhite9412801600100
Elegant vertical designer radiatorFlat panel. Double
White11003001600104
Elegant vertical designer radiator

Flat panel. Double


White12323001800106
Monster ShopOval tubes. DoubleWithheldWhite8132921500120
Monster ShopFlat panel. DoubleWithheldWhite10602801800135
Ultraheat-DR - Klon VerticalSquare tubes. DoubleChinaWhite8432311500138
Monster ShopTraditional. TripleWithheldWhite9142921800145
Ultraheat-DR - Klon VerticalSquare tubes. DoubleChinaWhite10892311800150
Radiator OutletOval tubes. Double
Grey8062361600150
Radiator OutletFlat panel. Double
White8702801600150
Radiator OutletFlat panel. Double.
Grey8702801600160
Radiator OutletFlat panel. Double
Grey9152801780160
Kartell Krad Aspen verticalFlat panel. DoubleChinaWhite10793001800173
UK Radiators TyphoonFlat panel. Double
White8022721800193
DeLonghiTraditional. TripleChina or EuropeWhite11643022000200
FlomastaFlat panel. DoubleUKWhite9632881800237Used to be called Moretti Modena
Terma ForteFlat panel. DoublePolandWhite8142921800282
Henrad Verona Slimline (Stelrad)SingleUKWhite8723201800350
Stelrad Compact VertexCompact. DoubleUKWhite11883001800543









Myson Premier CompactCompact. Double
White572300700144
Ultraheat Sofi VerticalOval tubes. Single
White528239180087
Radiator OutletOval tubes. Single
Grey551236160090
Monster ShopTraditional. Double
White645292150097
Ultraheat Tilbrook VerticalFlat on edge. Single
White5051561500108
Radiator OutletFlat panel. Single
Grey5232801780110
Radiator OutletOval tubes. Single
Grey5892361780110
Nordic OsloTraditional. Triple
White5041591800110
Monster ShopOval tubes. Double
White6462401600110
Monster ShopTraditional. Triple
White6092021800110
Ultraheat DR Linear VerticalFlat tubes. Double
White5302681800123
Eastbrook DR - MalmesburyOval tubes. Single
Grey5401851800161
Ultraheat Tilbrook VerticalFlat on edge. Single
White6181561800163

MARC (Manufacturers' Association of Radiators and Convectors) is a UK assocation "focussing on the specific needs of, and issues faced by, manufacturers and distributors of radiators with factories in the UK and/or Europe".
Members include: DQ HeatingEucothermIRSAP UK, MHS RadiatorsPurmo Group, StelradTerma Products UKUK Radiators, XimaxZehnder Group

DQ Heating is listed at Companies House as a wholesaler, not a manufacturer. Don't know who makes their radiators or where.

IRSAP is an Italian radiator manufacturer. They own The Radiator Company (use code EOCUC6ASDJ to get 10% off first order), Supplies4Heat, Radiators Direct (use code FIRST10 to get 10% off first order), and Clyde Radiators.

Purmo is group headquartered in Finland, and with manufacturing plants in UK and Germany (and probably other countries). They own the brands Radson, LVI, MMA, Vogel&Noot, Finimetal, Myson, Emmeti, Hewing, Sigarth, Barlo, Design by QRL and Merriott.

Terma is a Polish company.

UK Radiators is listed at Companies House as a wholesaler, not a manufacturer. Don't know who makes their radiators or where.

Ximax is an Austrian company. They have poor reviews on Trustpilot.

Zehnder is a Swiss company with manufacturing plants in Europe, North America and China.

DeLonghi is an Italian company with manufacuring plants in Europe and China.

Ultraheat is a division of Pitacs.
Pitacs is listed on Companies House as "Non-specialised wholesale trade" business. Most of the directors and people with significant control are Turkish.
They describe themselves as being founded as a "national distributor of heating products, when we launched our Ultraheat collection", and as having a "warehouse". These suggest that someone else manufactures their Ultraheat radiators. However, they also describe themselves as "one of the UK’s largest manufacturers and distributors of heating products", which implies that they manufacture at least some of their heating products.
They apparently have a "design and manufacturing facility in Turkey".

Performance with radiators installed for heat pump (plan SL)

Updated Feb 2025

This is the predicted performance of the radiators we have installed for use with the heat pump (installation completed 31 Jan 2025) based on my modelling (planSL.yaml). This includes additional back room and lounge radiators (see below) and a larger hall radiator,  This model splits the lounge into 3 areas: lounge entrance, lounge and lounge corner (to left of fireplace).

Setpoint is 21°C for all rooms, except for the lounge entrance at 21.6 and the bathroom at 22°C.
No heating in the ensuite.

RoomRadiatorRoom temperature @ -2°C outside and
radiator temperature 48°C
Room temperature @ -2°C outside and
radiator temperature 52°C
Room temperature @ -5°C outside and
radiator temperature 52°C
Lounge entranceK2 1800x600 2376W21.221.621.0
Lounge-20.720.620.5
Lounge cornerFlomasta K2 288x1800 963W20.821.021.0
Dining roomK2 700x800 1568W21.021.021.0
Back roomK2 600x900 1558W + K2 600x800 1385W = 2943W21.021.021.0
HallK2 600x900 1538W20.321.020.7
StudyK2 600x400 693W19.019.819.3
Front bedroomK2 450x1000 1371W20.621.020.9
Back bedroomK2 450x800 1096W20.020.820.2
Ensuite-18.919.618.9
Bathroom

K2 600x600 1039W

22.022.022.0
Kitchen-18.018.317.9
Total power
5445
2653 @ COP 2.09
5558
3021 @ COP 1.84
6152
3662 @ COP 1.68

Note that at -2°C outside, the Daikin heat pump is 13% more efficient at a flow temperature of 50°C (radiator temperature 48°C) than at 55°C (radiator temperature 52°C).

The Daikin heat pump was installed configured with a WD curve with a flow temperature of 50°C at -7°C outside, and a flow temperature of 25°C at 20°C outside. This produces a slope of (50-25)/(20- -7) = 0.93, and a flow temperature of 50 - (-2 - -7) * 0.93 = 45°C at -2°C outside.

The table below shpws minimum outside temperature for various flow temperatures (assuming radiator temperature is 2.5°C less than flow temperature), according to my model. For comparison, the corresponding outside temperatures using the Octopus WD configuration are also shown.

Flow temperature °COutside temperature °C
using my model
Outside temperature °C
using Octopus WD configuration
Power required kW
3021150.63
351691.69
401042.31
455-24.01
50-1-75.26
51-2
5.48
55-6-126.34
60-12
7.61
65-16
8.50
Slope0.930.93

Based on the model results, a possible WD configuration is flow 30°C at outside 21°C, and flow 55°C at -6°C. This gives a slope of 0.93.

Performance with extra back room radiator and bigger hall radiator (plan R)

Written Sep 2024

Installing a bigger hall radiator should help with the study, where a K3 radiator would be needed even with extra insulation. It should also help with the lounge (and other rooms to a lesser extent).

This is the predicted performance of the radiators we have had installed since Dec 2023 plus the additional back room radiator (see below) and a larger hall radiator, based on my modelling (planR.yaml).

Setpoint is 21°C for all rooms.
No heating in the ensuite.

RoomRadiatorRoom temperature @ -2°C outside and radiator temperature 52°CRoom temperature @ -2°C outside and radiator temperature 48°CRoom temperature @ -5°C outside and radiator temperature 52°CRoom temperature @ -5°C outside and radiator temperature 48°C
LoungeK2 1800x600 2376W21.020.620.819.7
Dining roomK2 700x800 1568W21.020.921.020.0
Back roomK2 600x900 1558W + K2 600x800 1385W = 2943W21.021.021.021.0
HallK2 600x1200 2078W21.021.021.020.2
StudyK2 600x400 693W19.719.319.318.4
Front bedroomK2 450x1000 1371W21.020.520.819.4
Back bedroomK2 450x800 1096W21.020.520.819.6
Ensuite-19.819.419.518.3
Bathroom

K2 600x600 1039W

21.021.021.021.0
Kitchen-18.017.817.616.8
Total power
5411533560015758

Radiator temperatures °C needed for various outside temperatures:

RoomRadiator-2°C outside0°C outside2°C outside7°C outside12°C outside
LoungeK2 1800x600 2376W5250484338
Dining roomK2 700x800 1568W4544423835
Back roomK2 600x900 1558W + K2 600x800 1385W = 2943W4039383532
HallK2 600x1200 2078W4140393532
StudyK2 600x400 693W6765625649
Front bedroomK2 450x1000 1371W5048464136
Back bedroomK2 450x800 1096W5048464136
Bathroom

K2 600x600 1039W

3938373532

Possible flow temperature5452504540

Performance with extra back room radiator (plan Q)

Written Sep 2024

Simon from Octopus calculated that we would need an extra K2 600x800 radiator in the back room.

This is the predicted performance of the radiators we have had installed since Dec 2023 plus the additional back room radiator, based on my modelling (planQ.yaml).

Setpoint is 21°C for all rooms.
No heating in the ensuite.

RoomRadiatorRoom temperature @ -2°C outside and radiator temperature 52°CRoom temperature @ -2°C outside and radiator temperature 48°CRoom temperature @ -5°C outside and radiator temperature 52°CRoom temperature @ -5°C outside and radiator temperature 48°C
LoungeK2 1800x600 2376W20.920.020.519.0
Dining roomK2 700x800 1568W21.020.320.919.3
Back roomK2 600x900 1558W + K2 600x800 1385W = 2943W21.021.021.021.0
HallT21 500x700 972W19.718.618.917.5
StudyK2 600x400 693W18.717.617.816.5
Front bedroomK2 450x1000 1371W21.020.020.418.9
Back bedroomK2 450x800 1096W21.020.120.519.0
Ensuite-19.818.919.217.8
Bathroom

K2 600x600 1039W

21.021.021.021.0
Kitchen-17.817.117.116.1
Total power
5343513058525533

Installed radiator performance

Written Sep 2024

Predicted performance using my model

This is the predicted performance of the radiators we have had installed since Dec 2023, based on my modelling (planL.yaml).

Setpoint is 21°C for all rooms.
150W towel in ensuite is assumed to be permanently on.


RoomRadiatorRoom temperature @ -2°C outside and radiator temperature 58°CRoom temperature @ -2°C outside and radiator temperature 52°CRoom temperature @ -5°C outside and radiator temperature 58°CRoom temperature @ -5°C outside and radiator temperature 52°C
LoungeK2 1800x600 2376W21.020.821.020.3
Dining roomK2 700x800 1568W21.021.021.020.7
Back roomK2 600x900 1558W21.020.921.020.3
HallT21 500x700 972W20.819.720.218.8
StudyK2 600x400 693W20.018.719.317.8
Front bedroomK2 450x1000 1371W21.021.021.020.4
Back bedroomK2 450x800 1096W21.021.020.920.3
EnsuiteTowel 150W20.720.719.520.5
Bathroom

K2 600x600 1039W

21.021.021.021.0
Kitchen-18.017.817.617.0
Total power
5515543661175947

This is the predicted performance of the radiators we have had installed since Dec 2023, with a 378W radiator added in the ensuite, based on my modelling (planL.yaml).

Setpoint is 21°C for all rooms.


RoomRadiatorRoom temperature @ -2°C outside and radiator temperature 58°CRoom temperature @ -2°C outside and radiator temperature 52°CRoom temperature @ -2°C outside and radiator temperature 48°CRoom temperature @ -5°C outside and radiator temperature 58°CRoom temperature @ -5°C outside and radiator temperature 52°CRoom temperature @ -5°C outside and radiator temperature 48°C
LoungeK2 1800x600 2376W21.020.820.021.020.318.7
Dining roomK2 700x800 1568W21.021.020.321.020.719.0
Back roomK2 600x900 1558W21.020.920.121.020.318.9
HallT21 500x700 972W20.819.718.620.218.817.3
StudyK2 600x400 693W20.018.717.619.317.816.3
Front bedroomK2 450x1000 1371W21.021.020.121.020.418.7
Back bedroomK2 450x800 1096W21.021.020.821.021.019.5
EnsuiteK1 450x500 378W21.021.020.621.020.819.3
Bathroom

K2 600x600 1039W

21.021.021.021.021.020.6
Kitchen-18.017.817.117.617.015.7
Total power
552154425162612659545546

Required flow temperature for Octopus 2022 heat losses

Assumptions:
Outside temperature -2°C.
MCS required temperatures.
Flow temperature is 3°C greater than the radiator temperature.
150W towel in ensuite is on.

RoomRequired temperature °CHeat loss kWRadiatorFactor needed (heat loss / rad power)ΔT to achieve factor °CRadiator temperature to achieve factor °CFlow temperature needed °C
Lounge / Dining room211993K2 1800x600 2376W + K2 700x800 1568W = 3994W0.50295053
Back room211134K2 600x900 1558W0.73396063
Hall18352T21 500x700 972W0.36234144
Study18270K2 600x400 693W0.39244245
Front bedroom18687K2 450x1000 1371W0.50294750
Back bedroom18493K2 450x800 1096W0.45274548
Bathroom22396

K2 600x600 1039W

0.38244649

According to Octopus's heat loss figures, the back room requires significant extra heating.
At a 50°C flow temperature and hence a radiator temperature of 48°C, ΔT is 27°C and the derating factor is 0.447.
Under these conditions the existing radiator would output 1558*0.447 = 696W. The heat loss is 1134, so an extra 1134-696 = 438W is needed.
This would require an extra radiator with a rating of 438/0.447 = 980W. A K2 600x600 is rated at 1039W. Simon on 12 Sep 2024 reckoned that a K2 600x800 @ 1385W would be needed for the heat loss he had calculated.

Required flow temperature for my heat losses

Updated Oct 2024

Assumptions:
Outside temperature -2°C.
All rooms at 21°C.
Flow temperature is 3°C greater than the radiator temperature.
150W towel in ensuite is on.

RoomRequired temperature °CHeat loss kWRadiatorFactor needed (heat loss / rad power)ΔT to achieve factor °CRadiator temperature to achieve factor °CFlow temperature needed °C
Lounge211250K2 1800x600 2376W
+ 420W = 2796W
+888W = 3264W
0.447
0.383
27
24
48
45
51
48
Dining room21603K2 700x800 1568W0.38244548
Back room21803K2 600x900 1558W +
K2 600x800 1368W = 2926W
0.27<20<42<45
Hall21619K2 600x800 1385W
K2 700x900 1764W
0.447
0.351
27
22
48
43
51
46
Study21628K2 600x400 693W0.91466770
Front bedroom21602K2 450x1000 1371W0.44274851
Back bedroom21497K2 450x800 1096W0.45274851
Bathroom21271

K2 600x600 1039W

0.26<20<42<45

Effect of hall setpoint on hall, study and lounge losses (signed figures are relative to 21°C):

Hall temperature °CHall loss kWStudy loss kWLounge loss kW
180
-619
891
+263
1456
+206
20302
-317
763
+135
1358
+108
21619
-0
628
-0
1250
-0
22937
+318
493
-135
1145
-105


Radiators for 55°C flow temperature

Written Sep 2023.

If we assume a 6°C drop through the radiators, the average radiator temperature will be 52°C for a flow temperature of 55°C.

For a room temperature of 21°C, ΔT will be 31°C and correction factor will be 0.534.
For a room temperature of 18°C, ΔT will be 34°C and correction factor will be 0.606.

Prices are from Stelrad website, including VAT. They could probably be bought cheaper elsewhere, and an installer wouldn't need to pay VAT.

Modelling was done using homeW52.yaml specification.

Radiators for 52°C radiator temperature
Room Heat loss W Rated power needed Existing radiators Possible radiators Price £ Room Temp
@ 55°C flow
Room Temp
@ 60°C flow
Lounge 21°C 1589 2976 T21 600x600 833W K2 1800x600 2376(1269)W 371
20.6 20.9
Dining room 21°C 616 1154 T21 600x600 833W K2 600x900 1558(832)W 121 21.0 21.0
Back room 21°C 884 1655 T11 600x900 923W K2 700x900 1764(942)W 140 21.0 21.0
Front bedroom 18°C 283 467 T11 400x700 460W [K1 400x700 460(279)W] 0 17.8 18.0
Back bedroom 18°C 133 219 T11 400x700 460W [K1 400x700 460(279)W] 0 18.0 18.0
Ensuite 21°C 231 433 Towel 150W [(150W)] 0 18.5 18.5
Hall 21°C 585 1096 T21 500x700 972W K2 600x700 1212(647)W 106 21.1 21.0
Study 21°C 471 882 T11 600x400 410W K2 700x400 784(419)W
98 20.1 21.0
Bathroom 21°C 309 577 Towel 1200x600 415W K2 600x400 693(370)W 76 21.0 21.0
Total
5101

5187 = 102% 912

Lounge radiator

The output of the specified vertical radiator isn't sufficient, but there isn't a proper alternative unless we are willing to install an extra radiator somewhere in the lounge. However, there are some things we can do to compensate for the low output.

Firstly, we can size the hall radiator for a temperature of 21°C (instead of the standard 18°C) to assist the lounge radiator (and the study radiator, which is also underpowered). We can also allow the hall temperature to rise above 21°C to allow extra heat to flow into the lounge and study. Anyway, in practice it would not be possible to maintain a 3°C difference between the hall and the other two rooms with open doorways. (I've tried sizing the hall radiator even larger, but it doesn't help much.)

Secondly, in cold weather we could raise the heat pump flow temperature to 60°C (say) to provide extra assistance.

Bathroom radiator

The available width between the door (open) and the bath is 600mm. The fittings each side of the radiator (TRV and lockshield) will need about 160mm, so the maximum radiator width is 400mm.

Radiators for 60°C flow temperature

Written Sep 2023.

If we assume a 6°C drop through the radiators, the average radiator temperature will be 57°C for a flow temperature of 60°C.

For a room temperature of 21°C, ΔT will be 36°C and correction factor will be 0.651.
For a room temperature of 18°C, ΔT will be 39°C and correction factor will be 0.723.

Prices are from Stelrad website, including VAT. They could probably be bought cheaper elsewhere, and an installer wouldn't need to pay VAT.

Modelling was done using homeW57.yaml specification.

Radiators for 57°C radiator temperature
Room Heat loss W Rated power needed Existing radiators Possible radiators Price £ Room Temp
Lounge 21°C 1589 2441 T21 600x600 833W K2 1800x600 2376(1547)W 371
20.9
Dining room 21°C 616 946 T21 600x600 833W K2 600x600 1039(676)W 97 21.0
Back room 21°C 884 1358 T11 600x900 923W K2 600x800 1385(902)W 118 21.0
Front bedroom 18°C 283 391 T11 400x700 460W [K1 400x700 460(279)W] 0 18.0
Back bedroom 18°C 133 184 T11 400x700 460W [K1 400x700 460(279)W] 0 18.0
Ensuite 21°C 231 355 Towel 150W [(150W)] 0 18.5
Hall 21°C 585 899 T21 500x700 972W [T21 500x700 972(633)W] 0 21.2
Study 21°C 471 724 T11 600x400 410W K2 700x400 784(510)W
98 21.0
Bathroom 21°C 309 475 Towel 1200x600 415W P+ 600x400 539(351)W 63 21.0
Total
5101

5399 = 106% 747

With these radiators, a radiator temperature of 48°C (flow temperature of 51°C) would be needed for an outside temperature of 7°C.

5 new radiators are needed, at a cost of £747, compared to 6 new radiators at a cost of £912 if we used a 55°C flow temperature.

A compromise might be to use the existing hall radiator and change the other 5 radiators to the 55°C flow specification. This would cost £806, i.e. £59 more than the 60°C flow specification, but £106 less than changing all 6 radiators. The hall radiator could be upgraded later if required.

The performance of this compromise would be:

Radiators for 52°C radiator temperature, original hall radiator
Room Heat loss W Rated power needed Existing radiators Possible radiators Price £ Room Temp
@ 55°C flow
Room Temp
@ 60°C flow
Lounge 21°C 1589 2976 T21 600x600 833W K2 1800x600 2376(1269)W 371
20.4 20.9
Dining room 21°C 616 1154 T21 600x600 833W K2 600x900 1558(832)W 121 20.9 21.0
Back room 21°C 884 1655 T11 600x900 923W K2 700x900 1764(942)W 140 21.0 21.0
Front bedroom 18°C 283 467 T11 400x700 460W [K1 400x700 460(279)W] 0 17.6 18.0
Back bedroom 18°C 133 219 T11 400x700 460W [K1 400x700 460(279)W] 0 18.0 18.0
Ensuite 21°C 231 433 Towel 150W [(150W)] 0 18.5 18.5
Hall 21°C 585 1096 T21 500x700 972W [T21 500x700 972(519)W] 0 20.2 21.2
Study 21°C 471 882 T11 600x400 410W K2 700x400 784(419)W
98 20.0 21.0
Bathroom 21°C 309 577 Towel 1200x600 415W K2 600x400 693(370)W 76 21.0 21.0
Total
5101

5059 = 99% 806

At 55°C flow, the lounge would be 0.2°C cooler and the study would be 0.1°C cooler than if the hall radiator was replaced. These differences would probably not be noticeable. The hall would be 0.9°C cooler.

At 60°C flow, the temperatues would be unchanged by not replacing the hall radiator.

With these radiators, a radiator temperature of 53°C (flow temperature of 56°C) would be needed for an outside temperature of 7°C.

Radiators for 65°C flow temperature

Written Sep 2023.

I am assuming a flow temperaure of 65°C and return temperature of 59°C, hence a radiator temperature of 62°C. This could be for the existing gas boiler (or a replacement boiler), or possibly for the Vaillant Arotherm plus heat pump.

For a room temperature of 21°C, ΔT will be 41°C and correction factor will be 0.771.
For a room temperature of 18°C, ΔT will be 44°C and correction factor will be 0.846.

Prices are from Stelrad website, including VAT. They could probably be bought cheaper elsewhere, and an installer wouldn't need to pay VAT.

Modelling was done using home W65.yaml specification.

Radiators for 62°C radiator temperature
Room Heat loss W Rated power needed W Existing radiators Possible radiators Price £ Room Temp °C
Lounge 21°C 1589 2061 T21 600x600 833W K2 1800x600 2376(1269)W 371
21.0
Dining room 21°C 616 799 T21 600x600 833W [T21 600x600 833(811)W] 0 21.0
Back room 21°C 884 1147 T11 600x900 923W K2 600x900 1572(1212)W 98 21.0
Front bedroom 18°C 283 335 T11 400x700 460W [T11 400x700 460(484)W] 0 18.0
Back bedroom 18°C 133 157 T11 400x700 460W [T11 400x700 460(484)W] 0 18.0
Ensuite 21°C 231 300 Towel 150W [(150W)] 0 18.5
Hall 21°C 585 759 T21 500x700 972W [T21 500x700 972(947)W] 0 21.0
Study 21°C 471 611 T11 600x400 410W K2 600x400 699(539)W 46 21.0
Bathroom 21°C 309 401 Towel 1200x600 415W [T11 600x400 410(316)W]
re-used from study
0 21.0
Total
5101

5427 = 106% 557

With these radiators, the table below shows the heating powers and radiator temperatures needed for the specified outside temperatures. The radiator temperature is based on the lounge radiator, which is the main limiting radiator. Flow temperatures for a heat pump would typically be about 3°C higher than the radiator temperature.

Outside temperature °C Power needed W Radiator temperature °C
-7 6119 64
-5 5655 61
-2 5104 59
0 4703 56
2 4298 55
3 4096 54
5 3691 52
7 3301 50
10 2710 46
12 2337 43
15 1765 39

Radiators for 70°C radiator temperature

Written Sep 2023.

I am assuming a flow temperaure of 75°C and return temperature of 65°C, hence a radiator temperature of 70°C. This could be for the existing gas boiler (or a replacement boiler), or possibly for the Vaillant Arotherm plus heat pump.

For a room temperature of 21°C, ΔT will be 49°C and correction factor will be 0.974.
For a room temperature of 18°C, ΔT will be 52°C and correction factor will be 1.052.

Prices are from Stelrad website, including VAT. They could probably be bought cheaper elsewhere, and an installer wouldn't need to pay VAT.

Modelling was done using home W70.yaml specification.

Radiators for 70°C radiator temperature
Room Heat loss W Rated power needed W Existing radiators Possible radiators Price £ Room Temp °C
Lounge 21°C 1589 1631 T21 600x600 833W K2 1800x600 2376(1269)W 371
21.0
Dining room 21°C 616 632 T21 600x600 833W [T21 600x600 833(811)W] 0 21.0
Back room 21°C 884 908 T11 600x900 923W [T11 600x900 923(899)W] 0 21.0
Front bedroom 18°C 283 269 T11 400x700 460W [T11 400x700 460(484)W] 0 18.0
Back bedroom 18°C 133 126 T11 400x700 460W [T11 400x700 460(484)W] 0 18.0
Ensuite 21°C 231 237 Towel 150W [(150W)] 0 18.5
Hall 21°C 585 601 T21 500x700 972W [T21 500x700 972(947)W] 0 21.0
Study 21°C 471 484 T11 600x400 410W T11 700x400 438(468)W 40 20.1
Bathroom 21°C 309 317 Towel 1200x600 415W [T11 600x400 410(399)W]
re-used from study
0 21.0
Total
5101

5427 = 106% 411

With these radiators, a radiator temperature of 58°C (flow temperature of 61°C) would be needed for an outside temperature of 7°C.

Octopus specifications

Octopus are sizing radiators assuming a flow temperature of 45°C.

The actual correction factors used by Octopus are 0.324 for a room temperature of 21°C and 0.386 for a room temperature of 18°C. These correspond to ΔT of 21.0°C and 24.0°C respectively, and hence to a radiator water temperature of 42.0°C in both cases.

Octopus specified radiators:

Room Description Design room temp °C Correction for low delta Room heat loss W Specified radiator output W at design temps Specified radiator output W at ΔT 50°C Correction factor for low ΔT Required radiator output W at ΔT 50°C Price inc VAT £
Lounge K2 Vert Radiator - H1800mm x L600mm 21.0 0.341 1993 773 2376 0.325 6151 371
Lounge K3 Radiator - H700mm x L1400mm 21.0 0.341 1993 1225 3797 0.323
459?
Back room K3 Radiator - H700mm x L1400mm 21.0 0.341 1134 1225 3797 0.323 3500 459?
Hall K2 Radiator - H600mm x L600mm 18.0 0.402 352 398 1039 0.383 912 92
Study K2 Radiator - H600mm x L400mm 18.0 0.402 270 261 693 0.377 699 71
Front bedroom K2 Radiator - H450mm x L1400mm 18.0 0.402 687 758 1919 0.395 1780 173
Back bedroom K2 Radiator - H450mm x L900mm 18.0 0.402 493 483 1234 0.391 1227 105
Ensuite
21.0
531




Bathroom
22.0
396





Total







1730

MCS Heat Emitter Guide

This is my attempt to size radiators and choose the flow temperature using the MCS Heat Emitter Guide (section 4 of MGD-007 Reference Data and Tools).

The guide uses an "Oversize Factor" (radiator rated output divided room heat loss) to look up the required flow temperature (or equivalently "star rating") using a graph. The graph corresponds to the first two columns in the following table:

Oversize factor Flow temperature Correction factor ΔT Room temperature
1.0
1.0 50
1.6 60 0.63 35 25
1.9 55 0.53 31 24
2.4 50 0.42 26 24
3.1 45 0.32 21 24
4.3 40 0.23 16 24
6.8 35 0.15 12 23

The third column is simply the reciprocal of the first column, and corresponds to the "Operating factor" in the Stelrad radiator temperature table. The fourth column is the difference between radiator temperature and room temperature, obtained by interpolating in the Stelrad table. The fifth column is the difference between the second and fourth columns.

Note that flow temperature is not the same as radiator temperature, since there is a temperature drop across the radiator. My guess is that MCS are assuming a room temperature of 20°C and a drop across the radiators of 8°C (although it could equally well be 21°C and 6°C respectively).

The first two columns can be approximated by:

FT = 27.8 + 52.3 / OF

Analysis of existing radiators:

Room Heat loss Radiator sizes Radiator output at ΔT 50°C Oversize factor Required flow temperature
Lounge 1993 P+ 600x600
P+ 600x600
1616 0.81 92
Back room 1134 K1 600x900 882 0.78 95
Front bedroom 687 K1 400x700 470 0.68 105
Back bedroom 493 K1 400x700 470 0.95 83
Hall 352 P+ 500x700 821 2.33 50
Study 270 K1 600x400 392 1.45 64
Bathroom 396 Towel 1200x600 415/616 1.04/1.56 78/61
Ensuite 531 Towel 700x400


The alternative output of 616W for the bathroom towel radiator is if we painted it white.

Analysis using 4.5 Guidance Table:

Room Heat loss Floor area Specific heat loss Guidance for 46-50°C flow Oversize factor for 46-50°C flow Guidance for 51-55°C flow Oversize factor for 51-55°C flow
Lounge 1993 22.9 87 Go ahead 2.4 Caution 1.9
Back room 1134 13.7 83 Go ahead 2.4 Caution 1.9
Front bedroom 687 11.2 61 Go ahead 2.4 Caution 1.9
Back bedroom 493 10.5 47 Go ahead 2.4 Caution 1.9
Hall 352 3.1 114 Caution 2.4 Caution 1.9
Study 270 2.7 100 Caution 2.4 Caution 1.9
Bathroom 396 3.2 124 Caution 2.4 Caution 1.9
Ensuite 531 4.7 113 Caution 2.4 Caution 1.9

The guidance in the MCS table is always "Caution" for flow temperatures of 51°C and above. The guidance for 46-50°C flow changes from "Go ahead" to "Caution" when the specific heat loss is 100 or above.
"Caution" means: "System can perform at these design conditions with extra consideration on the emitter and heat pump design sought from the specialist designer/manufacturer."

An "oversize factor" of 2.4 corresponds to a radiator correction factor 1/2.4 = 0.42.
An "oversize factor" of 1.9 corresponds to a radiator correction factor 1/1.9 = 0.53.
In my radiator design above, I am using correction factors in the range 0.43 to 0.49 for a flow temperature of 50°C, and 0.53 to 0.61 for a flow temperature of 55°C. The ranges are to cover varying target room temperatures.