Room | Inlet | TRV | |||
---|---|---|---|---|---|
Dining area | R | L | |||
Lounge | R | L | |||
Back room | R | R | |||
Bathroom | R | L | |||
Study | |||||
Hall | R | R | |||
Front bedroom | L | R | |||
Back bedroom | R | L |
According to BSRIA, BS EN 14511 (the standard used for testing heat pumps) specifies a flow temperature of 45°C and a return temperature of 40°C, i.e. a temperature drop across radiators of 5°C.
Octopus say they are sizing radiators using a "flow temperature" of 45°C. By studying the correction factors they are using (see beginning of the Radiators section below) they appear to be using a radiator temperature of 42°C. So they are presumably assuming a return temperature of 39°C, and a drop across the radiators of 6°C.
There seems to be a rule-of-thumb to use a drop through the radiators of 1/7 of the flow temperature, i.e. 7°C for 50°C flow and 8°C for 55°C. The government Report on compliance on page 63 uses 1/7 (quoting the original MCS Heat Emitter Guide), and Octopus's use of 6°C for 45°C flow and the general use of 10°C with 70°C flow are consistent with this. Hopefully this will not affect radiator sizes too much.
This rule-of-thumb doesn't make much sense to me. It would make more sense to use a fraction of the difference between the flow temperature and room temperature. The following table shows this fraction for various examples, assuming a room temperature of 20°C:
Flow temperature | Return temperature | Drop across radiators | ΔT | Fraction |
---|---|---|---|---|
45 | 40 | 5 | 25 | 0.2 |
45 | 39 | 6 | 25 | 0.24 |
70 | 60 | 10 | 50 | 0.2 |
Hello Renewables aim for a 50/55°C flow temperature. This would suggest drop of 10/11°C across the radiators and an average radiator temperature of 45/49.5°C. So using an average radiator temperature of 47°C for sizing radiators would be consistent with this aim.
The MCS certified products directory provides SCOP values for heat pumps at different flow temperatures. These values are lower than those in the Daikin product catalogue, so they are presumably for different conditions.
The MCS certification for the Daikin EDLQ07CAV3 Monobloc (as
used by Octopus) lists a SCOP of 3.57 at a flow temperature of
45°C.
The MCS certification for the Daikin ERGA06EVA heat pump provides the following table of SCOP values at different flow temperatures:
Flow temperature °C | SCOP |
---|---|
45 | 3.7 |
46 | 3.64 |
47 | 3.59 |
48 | 3.54 |
49 | 3.48 |
50 | 3.43 |
51 | 3.37 |
52 | 3.32 |
53 | 3.26 |
54 | 3.21 |
55 | 3.15 |
Using the Altherma M at a flow temperature of 45°C (as specified by Octopus) would produce a SCOP of 3.57.
Using the Altherma 3 R at a flow temperature of 50°C would
produce a SCOP of 3.43 (0.14 less than Octopus)
Using the Altherma 3 R at a flow temperature of 55°C would produce
a SCOP of 3.15 (0.42 less than Octopus).
Hello
Renewables aim for a 50/55°C flow temperature. According
to my flow
temperature notes above, this would suggest drop of
10/11°C across the radiators and an average radiator temperature of
45/49.5°C. So using a flow temperature of 52°C and an average
radiator temperature of 47°C for sizing radiators would be
consistent with this aim.
If we assume a 6°C drop through the radiators, the average radiator temperature will be 47/52°C for a flow temperature of 50/55°C.
Updated Sep 2023 to use later Stelrad table (slightly smaller factors) and add extra entries.
According to Stelrad a radiator specified at ΔT 50°C has to be derated by the factors in this table:
ΔT °C | Operating factor |
---|---|
20 | 0.302 |
21 | 0.322 |
22 | 0.342 |
23 | 0.363 |
24 | 0.383 |
25 | 0.404 |
26 | 0.426 |
27 | 0.447 |
28 | 0.469 |
29 | 0.491 |
30 | 0.513 |
31 | 0.535 |
32 | 0.558 |
33 | 0.581 |
34 | 0.604 |
35 | 0.626 |
36 | 0.651 |
37 | 0.675 |
38 | 0.699 |
39 | 0.723 |
40 | 0.747 |
Type | Description | Power density W/m² | Space between radiator and wall mm | Projection from wall mm | Pipe centres from wall mm | Water contents l/m² |
---|---|---|---|---|---|---|
K1 | Single panel, one set of fins | 1700 | 19 / 30 | 83 / 94 | 51 / 62 | 5.5 |
P+ | Double panel, one set of fins | 2460 | 23 / 34 | 101 / 112 | 62 / 73 | 11 |
K2 | Double panel, two sets of fins | 3130 | 22 / 33 | 124 / 135 | 73 / 84 | 11 |
K3 | Triple panel, three sets of fins | 3980 | 22 | 180 | 73 |
|
Where two figures are given for distances from the wall these correspond to two possible orientations of the mounting brackets.
Water contents figures are approximate. See table in this Stelrad document for more accurate figures, broken down by radiator height.
Weights in kg/m. I.e. multiply by radiator width to get radiator weight. Data from Stelrad Compact Horizontal and Compact K3 documents.
450mm height | 600mm height | 700mm height | 1800mm heght | |
---|---|---|---|---|
K1 | 14.51 | 19.70 | 22.90 | |
P+ | 22.04 | 29.80 | 34.50 | |
K2 | 25.90 | 35.00 | 40.53 | 88.8 |
K3 | 43.40 (500mm height) | 52.50 | 60.77 |
If the maximum radiator weight I can handle is 35kg, then the following table gives the maximum usable widths and corresponding powers:
450mm height | 600mm height | 700mm height | 1800mm height | |
---|---|---|---|---|
K1 | 2400mm 1814W |
1800mm 1764W |
1500mm 1563W |
|
P+ | 1500mm 1478W |
1100mm 1481W |
1000mm 1532W |
|
K2 | 1300mm 1645W |
1000mm 1732W |
800mm 1568W |
400mm 1584W |
K3 | 800mm (500mm height) 1645W |
600mm 1433W |
500mm 1356W |
Stelrad vertical radiators (Stelrad prices) | ||||
---|---|---|---|---|
Range | Type | Size mm | Power W | Price £ inc VAT |
Classic Compact Vertical | K2 | 1800 x 400 | 1584 | 308 |
Classic Compact Vertical | K2 | 1800 x 500 | 1980 | 339 |
Classic Compact Vertical | K2 | 1800 x 600 | 2376 | 371 |
Stelrad Classic Compact radiators (Stelrad prices) | |||
---|---|---|---|
Type | Size mm | Power W | Price £ inc VAT |
P+ | 600 x 400 | 539 | 60 |
K2 | 600 x 400 | 693 | 71 |
K2 | 700 x 400 | 784 | 98 |
K2 | 450 x 600 | 822 | 89 |
K2 | 600 x 700 | 1212 | 100 |
K2 | 450 x 900 | 1234 | 105 |
K2 | 600 x 800 | 1385 | 118 |
K2 | 700 x 700 | 1372 | 137 |
K2 | 600 x 900 | 1558 | 115 |
K2 | 700 x 800 | 1568 | 145 |
K2 | 450 x 1200 | 1645 | 135 |
K2 | 450 x 1000 | 1371 | 112 |
K2 | 600 x 1000 | 1732 | 122 |
K2 | 700 x 900 | 1764 | 157 |
P+ | 700 x 1200 | 1839 | 184 |
P+ | 600 x 1400 | 1885 | 167 |
K2 | 600 x 1100 | 1905 | 135 |
K2 | 450 x 1400 | 1919 | 173 |
K2 | 700 x 1000 | 1960 | 167 |
K2 | 600 x 1200 | 2078 | 147 |
K3 | 600 x 900 | 2150 | 212 |
K2 | 700 x 1100 | 2156 | 184 |
See Kudox Technical Data and Fitted Dimensions.
Type | Description | Power density W/m² | Space between radiator and wall mm | Projection from wall mm | Pipe centres from wall mm |
---|---|---|---|---|---|
T11 | Single panel, one set of fins | 1700 | 20 | 85 | 50 |
T21 | Double panel, one set of fins | 2460 | 31 | 101 | 66 |
T22 | Double panel, two sets of fins | 3130 | 31 | 135 | 83 |
T33 | Triple panel, three sets of fins | 3980 | 31 | 191 |
83 |
Some measurements for 15mm pipe and compression fittings:
Pipe clip: pipe centre to wall:
19mm
Pipe clip: total projection from wall: 27mm
Pipe insertion depth: 14mm
Pipe insertion depth to face of untightened nut): 22mm
Elbow: overall size: 45mm
Elbow: pipe centre to face of other nut (untightened): 30mm
Pair of elbows: minimum distance between pipe centres: 60mm
Pair of elbows: pipe length for minimum distance between pipe
centres: 44mm
Elbow: pipe end to centre of other pipe: 7mm
Elbow: projection of pipe from wall to join pipe clipped to wall:
19-7 = 12mm
The measurement for elbows also appy to tees and radiator valves.
Radiator pipe centres are approximately 25mm above the bottom of the radiator.
If we have a pipe clipped to a wall, and use two elbows to move the pipe away from the wall, the moved pipe centre will be at least 19+60 = 79mm away from the wall.
If this two-elbow method is used to connect to a K2 radiator, the radiator support brackets must be used to provide pipe centres 84mm from the wall. Note that with the brackets this way round, there will be 33mm space between the radiator and the wall - not enough to fit an elbow in. The radiator pipe centres would need to be at least 3x30 = 90mm above the horizontal wall pipe centres (30mm for each elbow, and 30mm for the valve bend).
The two-elbow method can't be used to connect to a P+ radiator, since the radiator support brackets can only provide pipe centres 62mm or 73mm from the wall. In this case, the radiator valves could be angled so that the pipes below them go back to elbows on the horizontal pipes clipped to the wall. The angle would need to handle an offset of 62-19 = 43mm. To keep the angle reasonable, the vertical distance between the radiator pipe centre and the horizontal pipe centre should be at least double this offset, i.e. at least 86mm. This would put the bottom of the radiator at least 86-25 = 61mm above the horizontal pipe centre.
If we wanted to use the angle method with a K2 radiator, the offset would be 73-19 = 54mm and the vertical distance would need to be at least 108mm, putting the bottom of the radiator at least 108-25 = 83mm above the horizontal pipe centre.
Updated Oct 2024:.
This table shows the heat losses at various outdoor temperatures according to my latest heat model (lossSL.yaml).
The ensuite and study doors are assumed to be open (assumed closed before Aug 2024).
All setpoints are assumed to be 21°C, except for the lounge entrance at 21.6 (MCS setpoints assumed before Aug 2024).
Heat losses for various outdoor temperatures | |||||||||
---|---|---|---|---|---|---|---|---|---|
Room | -10°C | -7°C | -5°C | -2°C | 0°C | 2°C | 7°C | 10°C | 15°C |
Lounge entrance | 1158 | 1085 | |||||||
Lounge corner | 506 | 437 | |||||||
Dining room | 676 | 596 | |||||||
Back room | 876 | 788 | |||||||
Front bedroom | 646 | 569 | |||||||
Back bedroom | 527 | 464 | |||||||
Hall | 764 | 676 | |||||||
Study | 723 | 655 | |||||||
Bathroom | 284 | 255 | |||||||
Ensuite | 234 | 207 | |||||||
Total |
6393 | 5732 |
Total heat loss varies by 210W/°C for outside temperatures in range -5°C to 10°C, and can be approximated by 5053-210*T, where T is outside temperature.
We currently don't have a radiator in the ensuite (apart from the towel radiator), but we could install one. To handle the 200W heat loss at -2°C with a radiator temperature of 48°C and a room temperature of 21°C, we would need a radiator rated at 200/0.447 = 447W. A K1 450x600 radiator is rated at 454W.
Simon on 12 Sep 2024 calculated the ensuite loss at 300W, for which we would need a radiator rated at 300/0.447 = 671W. This would require a K1 600x700 @ 686W, or one of our spare P+ 600x600 @ 808W, or a K2 450x500 @ 685W.
To handle the 633W loss in the study at a radiator temperure of 48°C would require a radiator rated at 633/.447 = 1416W. The most powerful radiator we could install in the available width is a K3 600x400 rated at 956W. This would require a derating of at most 633/956 = 0.662, which corresponds to a ΔT of 36°C and hence a radiator temperature of 21+36 = 57°C.
Insulating both the ceiling and the garage wall of the study could reduce the loss to about 452W. With a K3 600x400 this would require a derating of at most 452/956 = 0.473, which corresponds to a ΔT of 28°C and hence a radiator temperature of 21+28 = 49°C.
Written Sep 2024
This section compares the possible radiator changes investigated in the following sections. The possibilities are:
Plan Q adds a radiator in the back room to the existing set (minimum requirement for Octopus 2024).
Plan R is like plan Q but with a larger hall radiator.
Plan SL is like plan R but with an extra radiator in the lounge, and not such a big hall radiator.
Red cells indicate rooms where the temperature is more than 0.2°C below the target temperature (i.e. 20.7°C or less).
This table shows room temperatures with a radiator temperature of 48°C (flow temperature 50°C) and outside temperature of -2°C.
Room | Plan SL | Plan R | Plan Q |
---|---|---|---|
Lounge entrance | 21.4 | ||
Lounge | 20.8 | 20.6 | 20.0 |
Lounge corner | 21.0 | ||
Dining room | 21.0 | 20.9 | 20.3 |
Back room | 21.0 | 21.0 | 21.0 |
Hall | 20.6 | 21.0 | 18.6 |
Study | 19.1 | 19.3 | 17.6 |
Front bedroom | 20.8 | 20.5 | 20.0 |
Back bedroom | 20.8 | 20.5 | 20.1 |
Ensuite | 19.6 | 19.4 | 18.9 |
Bathroom | 21.0 | 21.0 | 21.0 |
Kitchen | 18.1 | 17.8 | 17.1 |
This table shows room temperatures with a radiator temperature of 52°C (flow temperature 55°C) and outside temperature of -5°C.
Room | Plan SL | Plan R | Plan Q |
---|---|---|---|
Lounge entrance | 21.7 | ||
Lounge | 20.9 | 20.8 | 20.5 |
Lounge corner | 21.0 | ||
Dining room | 21.0 | 21.0 | 20.9 |
Back room | 21.0 | 21.0 | 21.0 |
Hall | 21.0 | 21.0 | 18.9 |
Study | 19.3 | 19.3 | 17.8 |
Front bedroom | 21.0 | 20.8 | 20.4 |
Back bedroom | 21.0 | 20.8 | 20.5 |
Ensuite | 19.7 | 19.5 | 19.2 |
Bathroom | 21.0 | 21.0 | 21.0 |
Kitchen | 18.0 | 17.6 | 17.1 |
The current radiators have a combined rated power of 3944W, which provides
The original Octopus specification had a heat loss of 1993W, which requires rated power of 6151W at a flow temperature of 45°C.
Possible radiators to go in corner of lounge to left of fireplace:
Radiator | Type | Country | Colour | Rated power W | Width mm | Height mm | Price £ | Comments |
---|---|---|---|---|---|---|---|---|
Monster Shop | Flat panel. Double | Withheld | White | 941 | 280 | 1600 | 100 | |
Elegant vertical designer radiator | Flat panel. Double | White | 1100 | 300 | 1600 | 104 | ||
Elegant vertical designer radiator | Flat panel. Double | White | 1232 | 300 | 1800 | 106 | ||
Monster Shop | Oval tubes. Double | Withheld | White | 813 | 292 | 1500 | 120 | |
Monster Shop | Flat panel. Double | Withheld | White | 1060 | 280 | 1800 | 135 | |
Ultraheat-DR - Klon Vertical | Square tubes. Double | China | White | 843 | 231 | 1500 | 138 | |
Monster Shop | Traditional. Triple | Withheld | White | 914 | 292 | 1800 | 145 | |
Ultraheat-DR - Klon Vertical | Square tubes. Double | China | White | 1089 | 231 | 1800 | 150 | |
Radiator Outlet | Oval tubes. Double | Grey | 806 | 236 | 1600 | 150 | ||
Radiator Outlet | Flat panel. Double | White | 870 | 280 | 1600 | 150 | ||
Radiator Outlet | Flat panel. Double. | Grey | 870 | 280 | 1600 | 160 | ||
Radiator Outlet | Flat panel. Double | Grey | 915 | 280 | 1780 | 160 | ||
Kartell Krad Aspen vertical | Flat panel. Double | China | White | 1079 | 300 | 1800 | 173 | |
UK Radiators Typhoon | Flat panel. Double | White | 802 | 272 | 1800 | 193 | ||
DeLonghi | Traditional. Triple | China or Europe | White | 1164 | 302 | 2000 | 200 | |
Flomasta | Flat panel. Double | UK | White | 963 | 288 | 1800 | 237 | Used to be called Moretti Modena |
Terma Forte | Flat panel. Double | Poland | White | 814 | 292 | 1800 | 282 | |
Henrad Verona Slimline (Stelrad) | Single | UK | White | 872 | 320 | 1800 | 350 | |
Stelrad Compact Vertex | Compact. Double | UK | White | 1188 | 300 | 1800 | 543 | |
Myson Premier Compact | Compact. Double | White | 572 | 300 | 700 | 144 | ||
Ultraheat Sofi Vertical | Oval tubes. Single | White | 528 | 239 | 1800 | 87 | ||
Radiator Outlet | Oval tubes. Single | Grey | 551 | 236 | 1600 | 90 | ||
Monster Shop | Traditional. Double | White | 645 | 292 | 1500 | 97 | ||
Ultraheat Tilbrook Vertical | Flat on edge. Single | White | 505 | 156 | 1500 | 108 | ||
Radiator Outlet | Flat panel. Single | Grey | 523 | 280 | 1780 | 110 | ||
Radiator Outlet | Oval tubes. Single | Grey | 589 | 236 | 1780 | 110 | ||
Nordic Oslo | Traditional. Triple | White | 504 | 159 | 1800 | 110 | ||
Monster Shop | Oval tubes. Double | White | 646 | 240 | 1600 | 110 | ||
Monster Shop | Traditional. Triple | White | 609 | 202 | 1800 | 110 | ||
Ultraheat DR Linear Vertical | Flat tubes. Double | White | 530 | 268 | 1800 | 123 | ||
Eastbrook DR - Malmesbury | Oval tubes. Single | Grey | 540 | 185 | 1800 | 161 | ||
Ultraheat Tilbrook Vertical | Flat on edge. Single | White | 618 | 156 | 1800 | 163 |
MARC (Manufacturers' Association of Radiators and Convectors) is a UK assocation "focussing on the specific needs of, and issues faced by, manufacturers and distributors of radiators with factories in the UK and/or Europe".
Members include: DQ Heating, Eucotherm, IRSAP UK, MHS Radiators, Purmo Group, Stelrad, Terma Products UK, UK Radiators, Ximax, Zehnder Group
DQ Heating is listed at Companies House as a wholesaler, not a manufacturer. Don't know who makes their radiators or where.
IRSAP is an Italian radiator manufacturer. They own The Radiator Company (use code EOCUC6ASDJ to get 10% off first order), Supplies4Heat, Radiators Direct (use code FIRST10 to get 10% off first order), and Clyde Radiators.
Purmo is group headquartered in Finland, and with manufacturing plants in UK and Germany (and probably other countries). They own the brands Radson, LVI, MMA, Vogel&Noot, Finimetal, Myson, Emmeti, Hewing, Sigarth, Barlo, Design by QRL and Merriott.
Terma is a Polish company.
UK Radiators is listed at Companies House as a wholesaler, not a manufacturer. Don't know who makes their radiators or where.
Ximax is an Austrian company. They have poor reviews on Trustpilot.
Zehnder is a Swiss company with manufacturing plants in Europe, North America and China.
DeLonghi is an Italian company with manufacuring plants in Europe and China.
Ultraheat is a division of Pitacs.
Pitacs is listed on Companies House as "Non-specialised wholesale trade" business. Most of the directors and people with significant control are Turkish.
They describe themselves as being founded as a "national distributor of heating products, when we launched our Ultraheat collection", and as having a "warehouse". These suggest that someone else manufactures their Ultraheat radiators. However, they also describe themselves as "one of the UK’s largest manufacturers and distributors of heating products", which implies that they manufacture at least some of their heating products.
They apparently have a "design and manufacturing facility in Turkey".
Updated Feb 2025
This is the predicted performance of the radiators we have installed for use with the heat pump (installation completed 31 Jan 2025) based on my modelling (planSL.yaml). This includes additional back room and lounge radiators (see below) and a larger hall radiator, This model splits the lounge into 3 areas: lounge entrance, lounge and lounge corner (to left of fireplace).
Setpoint is 21°C for all rooms, except for the lounge entrance at 21.6 and the bathroom at 22°C.
No heating in the ensuite.
Room | Radiator | Room temperature @ -2°C outside and radiator temperature 48°C | Room temperature @ -2°C outside and radiator temperature 52°C | Room temperature @ -5°C outside and radiator temperature 52°C |
---|---|---|---|---|
Lounge entrance | K2 1800x600 2376W | 21.2 | 21.6 | 21.0 |
Lounge | - | 20.7 | 20.6 | 20.5 |
Lounge corner | Flomasta K2 288x1800 963W | 20.8 | 21.0 | 21.0 |
Dining room | K2 700x800 1568W | 21.0 | 21.0 | 21.0 |
Back room | K2 600x900 1558W + K2 600x800 1385W = 2943W | 21.0 | 21.0 | 21.0 |
Hall | K2 600x900 1538W | 20.3 | 21.0 | 20.7 |
Study | K2 600x400 693W | 19.0 | 19.8 | 19.3 |
Front bedroom | K2 450x1000 1371W | 20.6 | 21.0 | 20.9 |
Back bedroom | K2 450x800 1096W | 20.0 | 20.8 | 20.2 |
Ensuite | - | 18.9 | 19.6 | 18.9 |
Bathroom | K2 600x600 1039W | 22.0 | 22.0 | 22.0 |
Kitchen | - | 18.0 | 18.3 | 17.9 |
Total power | 5445 2653 @ COP 2.09 | 5558 3021 @ COP 1.84 | 6152 3662 @ COP 1.68 |
Note that at -2°C outside, the Daikin heat pump is 13% more efficient at a flow temperature of 50°C (radiator temperature 48°C) than at 55°C (radiator temperature 52°C).
The Daikin heat pump was installed configured with a WD curve with a flow temperature of 50°C at -7°C outside, and a flow temperature of 25°C at 20°C outside. This produces a slope of (50-25)/(20- -7) = 0.93, and a flow temperature of 50 - (-2 - -7) * 0.93 = 45°C at -2°C outside.
The table below shpws minimum outside temperature for various flow temperatures (assuming radiator temperature is 2.5°C less than flow temperature), according to my model. For comparison, the corresponding outside temperatures using the Octopus WD configuration are also shown.
Flow temperature °C | Outside temperature °C using my model | Outside temperature °C using Octopus WD configuration | Power required kW |
---|---|---|---|
30 | 21 | 15 | 0.63 |
35 | 16 | 9 | 1.69 |
40 | 10 | 4 | 2.31 |
45 | 5 | -2 | 4.01 |
50 | -1 | -7 | 5.26 |
51 | -2 | 5.48 | |
55 | -6 | -12 | 6.34 |
60 | -12 | 7.61 | |
65 | -16 | 8.50 | |
Slope | 0.93 | 0.93 |
Based on the model results, a possible WD configuration is flow 30°C at outside 21°C, and flow 55°C at -6°C. This gives a slope of 0.93.
Written Sep 2024
Installing a bigger hall radiator should help with the study, where a K3 radiator would be needed even with extra insulation. It should also help with the lounge (and other rooms to a lesser extent).
This is the predicted performance of the radiators we have had installed since Dec 2023 plus the additional back room radiator (see below) and a larger hall radiator, based on my modelling (planR.yaml).
Setpoint is 21°C for all rooms.
No heating in the ensuite.
Room | Radiator | Room temperature @ -2°C outside and radiator temperature 52°C | Room temperature @ -2°C outside and radiator temperature 48°C | Room temperature @ -5°C outside and radiator temperature 52°C | Room temperature @ -5°C outside and radiator temperature 48°C |
---|---|---|---|---|---|
Lounge | K2 1800x600 2376W | 21.0 | 20.6 | 20.8 | 19.7 |
Dining room | K2 700x800 1568W | 21.0 | 20.9 | 21.0 | 20.0 |
Back room | K2 600x900 1558W + K2 600x800 1385W = 2943W | 21.0 | 21.0 | 21.0 | 21.0 |
Hall | K2 600x1200 2078W | 21.0 | 21.0 | 21.0 | 20.2 |
Study | K2 600x400 693W | 19.7 | 19.3 | 19.3 | 18.4 |
Front bedroom | K2 450x1000 1371W | 21.0 | 20.5 | 20.8 | 19.4 |
Back bedroom | K2 450x800 1096W | 21.0 | 20.5 | 20.8 | 19.6 |
Ensuite | - | 19.8 | 19.4 | 19.5 | 18.3 |
Bathroom | K2 600x600 1039W | 21.0 | 21.0 | 21.0 | 21.0 |
Kitchen | - | 18.0 | 17.8 | 17.6 | 16.8 |
Total power | 5411 | 5335 | 6001 | 5758 |
Radiator temperatures °C needed for various outside temperatures:
Room | Radiator | -2°C outside | 0°C outside | 2°C outside | 7°C outside | 12°C outside |
---|---|---|---|---|---|---|
Lounge | K2 1800x600 2376W | 52 | 50 | 48 | 43 | 38 |
Dining room | K2 700x800 1568W | 45 | 44 | 42 | 38 | 35 |
Back room | K2 600x900 1558W + K2 600x800 1385W = 2943W | 40 | 39 | 38 | 35 | 32 |
Hall | K2 600x1200 2078W | 41 | 40 | 39 | 35 | 32 |
Study | K2 600x400 693W | 67 | 65 | 62 | 56 | 49 |
Front bedroom | K2 450x1000 1371W | 50 | 48 | 46 | 41 | 36 |
Back bedroom | K2 450x800 1096W | 50 | 48 | 46 | 41 | 36 |
Bathroom | K2 600x600 1039W | 39 | 38 | 37 | 35 | 32 |
Possible flow temperature | 54 | 52 | 50 | 45 | 40 |
Written Sep 2024
Simon from Octopus calculated that we would need an extra K2 600x800 radiator in the back room.
This is the predicted performance of the radiators we have had installed since Dec 2023 plus the additional back room radiator, based on my modelling (planQ.yaml).
Setpoint is 21°C for all rooms.
No heating in the ensuite.
Room | Radiator | Room temperature @ -2°C outside and radiator temperature 52°C | Room temperature @ -2°C outside and radiator temperature 48°C | Room temperature @ -5°C outside and radiator temperature 52°C | Room temperature @ -5°C outside and radiator temperature 48°C |
---|---|---|---|---|---|
Lounge | K2 1800x600 2376W | 20.9 | 20.0 | 20.5 | 19.0 |
Dining room | K2 700x800 1568W | 21.0 | 20.3 | 20.9 | 19.3 |
Back room | K2 600x900 1558W + K2 600x800 1385W = 2943W | 21.0 | 21.0 | 21.0 | 21.0 |
Hall | T21 500x700 972W | 19.7 | 18.6 | 18.9 | 17.5 |
Study | K2 600x400 693W | 18.7 | 17.6 | 17.8 | 16.5 |
Front bedroom | K2 450x1000 1371W | 21.0 | 20.0 | 20.4 | 18.9 |
Back bedroom | K2 450x800 1096W | 21.0 | 20.1 | 20.5 | 19.0 |
Ensuite | - | 19.8 | 18.9 | 19.2 | 17.8 |
Bathroom | K2 600x600 1039W | 21.0 | 21.0 | 21.0 | 21.0 |
Kitchen | - | 17.8 | 17.1 | 17.1 | 16.1 |
Total power | 5343 | 5130 | 5852 | 5533 |
Written Sep 2024
This is the predicted performance of the radiators we have had installed since Dec 2023, based on my modelling (planL.yaml).
Setpoint is 21°C for all rooms.
150W towel in ensuite is assumed to be permanently on.
Room | Radiator | Room temperature @ -2°C outside and radiator temperature 58°C | Room temperature @ -2°C outside and radiator temperature 52°C | Room temperature @ -5°C outside and radiator temperature 58°C | Room temperature @ -5°C outside and radiator temperature 52°C |
---|---|---|---|---|---|
Lounge | K2 1800x600 2376W | 21.0 | 20.8 | 21.0 | 20.3 |
Dining room | K2 700x800 1568W | 21.0 | 21.0 | 21.0 | 20.7 |
Back room | K2 600x900 1558W | 21.0 | 20.9 | 21.0 | 20.3 |
Hall | T21 500x700 972W | 20.8 | 19.7 | 20.2 | 18.8 |
Study | K2 600x400 693W | 20.0 | 18.7 | 19.3 | 17.8 |
Front bedroom | K2 450x1000 1371W | 21.0 | 21.0 | 21.0 | 20.4 |
Back bedroom | K2 450x800 1096W | 21.0 | 21.0 | 20.9 | 20.3 |
Ensuite | Towel 150W | 20.7 | 20.7 | 19.5 | 20.5 |
Bathroom | K2 600x600 1039W | 21.0 | 21.0 | 21.0 | 21.0 |
Kitchen | - | 18.0 | 17.8 | 17.6 | 17.0 |
Total power | 5515 | 5436 | 6117 | 5947 |
This is the predicted performance of the radiators we have had installed since Dec 2023, with a 378W radiator added in the ensuite, based on my modelling (planL.yaml).
Setpoint is 21°C for all rooms.
Room | Radiator | Room temperature @ -2°C outside and radiator temperature 58°C | Room temperature @ -2°C outside and radiator temperature 52°C | Room temperature @ -2°C outside and radiator temperature 48°C | Room temperature @ -5°C outside and radiator temperature 58°C | Room temperature @ -5°C outside and radiator temperature 52°C | Room temperature @ -5°C outside and radiator temperature 48°C |
---|---|---|---|---|---|---|---|
Lounge | K2 1800x600 2376W | 21.0 | 20.8 | 20.0 | 21.0 | 20.3 | 18.7 |
Dining room | K2 700x800 1568W | 21.0 | 21.0 | 20.3 | 21.0 | 20.7 | 19.0 |
Back room | K2 600x900 1558W | 21.0 | 20.9 | 20.1 | 21.0 | 20.3 | 18.9 |
Hall | T21 500x700 972W | 20.8 | 19.7 | 18.6 | 20.2 | 18.8 | 17.3 |
Study | K2 600x400 693W | 20.0 | 18.7 | 17.6 | 19.3 | 17.8 | 16.3 |
Front bedroom | K2 450x1000 1371W | 21.0 | 21.0 | 20.1 | 21.0 | 20.4 | 18.7 |
Back bedroom | K2 450x800 1096W | 21.0 | 21.0 | 20.8 | 21.0 | 21.0 | 19.5 |
Ensuite | K1 450x500 378W | 21.0 | 21.0 | 20.6 | 21.0 | 20.8 | 19.3 |
Bathroom | K2 600x600 1039W | 21.0 | 21.0 | 21.0 | 21.0 | 21.0 | 20.6 |
Kitchen | - | 18.0 | 17.8 | 17.1 | 17.6 | 17.0 | 15.7 |
Total power | 5521 | 5442 | 5162 | 6126 | 5954 | 5546 |
Assumptions:
Outside temperature -2°C.
MCS required temperatures.
Flow temperature is 3°C greater than the radiator temperature.
150W towel in ensuite is on.
Room | Required temperature °C | Heat loss kW | Radiator | Factor needed (heat loss / rad power) | ΔT to achieve factor °C | Radiator temperature to achieve factor °C | Flow temperature needed °C |
---|---|---|---|---|---|---|---|
Lounge / Dining room | 21 | 1993 | K2 1800x600 2376W + K2 700x800 1568W = 3994W | 0.50 | 29 | 50 | 53 |
Back room | 21 | 1134 | K2 600x900 1558W | 0.73 | 39 | 60 | 63 |
Hall | 18 | 352 | T21 500x700 972W | 0.36 | 23 | 41 | 44 |
Study | 18 | 270 | K2 600x400 693W | 0.39 | 24 | 42 | 45 |
Front bedroom | 18 | 687 | K2 450x1000 1371W | 0.50 | 29 | 47 | 50 |
Back bedroom | 18 | 493 | K2 450x800 1096W | 0.45 | 27 | 45 | 48 |
Bathroom | 22 | 396 | K2 600x600 1039W | 0.38 | 24 | 46 | 49 |
According to Octopus's heat loss figures, the back room requires significant extra heating.
At a 50°C flow temperature and hence a radiator temperature of 48°C, ΔT is 27°C and the derating factor is 0.447.
Under these conditions the existing radiator would output 1558*0.447 = 696W. The heat loss is 1134, so an extra 1134-696 = 438W is needed.
This would require an extra radiator with a rating of 438/0.447 = 980W. A K2 600x600 is rated at 1039W. Simon on 12 Sep 2024 reckoned that a K2 600x800 @ 1385W would be needed for the heat loss he had calculated.
Updated Oct 2024
Assumptions:
Outside temperature -2°C.
All rooms at 21°C.
Flow temperature is 3°C greater than the radiator temperature.
150W towel in ensuite is on.
Room | Required temperature °C | Heat loss kW | Radiator | Factor needed (heat loss / rad power) | ΔT to achieve factor °C | Radiator temperature to achieve factor °C | Flow temperature needed °C |
---|---|---|---|---|---|---|---|
Lounge | 21 | 1250 | K2 1800x600 2376W + 420W = 2796W +888W = 3264W | 0.447 0.383 | 27 24 | 48 45 | 51 48 |
Dining room | 21 | 603 | K2 700x800 1568W | 0.38 | 24 | 45 | 48 |
Back room | 21 | 803 | K2 600x900 1558W + K2 600x800 1368W = 2926W | 0.27 | <20 | <42 | <45 |
Hall | 21 | 619 | K2 600x800 1385W K2 700x900 1764W | 0.447 0.351 | 27 22 | 48 43 | 51 46 |
Study | 21 | 628 | K2 600x400 693W | 0.91 | 46 | 67 | 70 |
Front bedroom | 21 | 602 | K2 450x1000 1371W | 0.44 | 27 | 48 | 51 |
Back bedroom | 21 | 497 | K2 450x800 1096W | 0.45 | 27 | 48 | 51 |
Bathroom | 21 | 271 | K2 600x600 1039W | 0.26 | <20 | <42 | <45 |
Effect of hall setpoint on hall, study and lounge losses (signed figures are relative to 21°C):
Hall temperature °C | Hall loss kW | Study loss kW | Lounge loss kW |
---|---|---|---|
18 | 0 -619 | 891 +263 | 1456 +206 |
20 | 302 -317 | 763 +135 | 1358 +108 |
21 | 619 -0 | 628 -0 | 1250 -0 |
22 | 937 +318 | 493 -135 | 1145 -105 |
Written Sep 2023.
If we assume a 6°C drop through the radiators, the average
radiator temperature will be 52°C for a flow temperature of
55°C.
For a room temperature of 21°C, ΔT will be 31°C and correction
factor will be 0.534.
For a room temperature of 18°C, ΔT will be 34°C and correction
factor will be 0.606.
Prices are from Stelrad website, including VAT. They could probably be bought cheaper elsewhere, and an installer wouldn't need to pay VAT.
Modelling was done using homeW52.yaml specification.
Radiators for 52°C radiator temperature | |||||||
---|---|---|---|---|---|---|---|
Room | Heat loss W | Rated power needed | Existing radiators | Possible radiators | Price £ | Room Temp @ 55°C flow |
Room Temp @ 60°C flow |
Lounge 21°C | 1589 | 2976 | T21 600x600 833W | K2 1800x600 2376(1269)W |
371 |
20.6 | 20.9 |
Dining room 21°C | 616 | 1154 | T21 600x600 833W | K2 600x900 1558(832)W | 121 | 21.0 | 21.0 |
Back room 21°C | 884 | 1655 | T11 600x900 923W | K2 700x900 1764(942)W | 140 | 21.0 | 21.0 |
Front bedroom 18°C | 283 | 467 | T11 400x700 460W | [K1 400x700 460(279)W] | 0 | 17.8 | 18.0 |
Back bedroom 18°C | 133 | 219 | T11 400x700 460W | [K1 400x700 460(279)W] | 0 | 18.0 | 18.0 |
Ensuite 21°C | 231 | 433 | Towel 150W | [(150W)] | 0 | 18.5 | 18.5 |
Hall 21°C | 585 | 1096 | T21 500x700 972W | K2 600x700 1212(647)W | 106 | 21.1 | 21.0 |
Study 21°C | 471 | 882 | T11 600x400 410W | K2
700x400 784(419)W |
98 | 20.1 | 21.0 |
Bathroom 21°C | 309 | 577 | Towel 1200x600 415W | K2 600x400 693(370)W | 76 | 21.0 | 21.0 |
Total |
5101 |
|
|
5187 = 102% | 912 |
|
|
The output of the specified vertical radiator isn't sufficient, but there isn't a proper alternative unless we are willing to install an extra radiator somewhere in the lounge. However, there are some things we can do to compensate for the low output.
Firstly, we can size the hall radiator for a temperature of 21°C (instead of the standard 18°C) to assist the lounge radiator (and the study radiator, which is also underpowered). We can also allow the hall temperature to rise above 21°C to allow extra heat to flow into the lounge and study. Anyway, in practice it would not be possible to maintain a 3°C difference between the hall and the other two rooms with open doorways. (I've tried sizing the hall radiator even larger, but it doesn't help much.)
Secondly, in cold weather we could raise the heat pump flow temperature to 60°C (say) to provide extra assistance.
The available width between the door (open) and the bath is 600mm. The fittings each side of the radiator (TRV and lockshield) will need about 160mm, so the maximum radiator width is 400mm.
Written Sep 2023.
If we assume a 6°C drop through the radiators, the average
radiator temperature will be 57°C for a flow temperature of
60°C.
For a room temperature of 21°C, ΔT will be 36°C and correction
factor will be 0.651.
For a room temperature of 18°C, ΔT will be 39°C and correction
factor will be 0.723.
Prices are from Stelrad website, including VAT. They could probably be bought cheaper elsewhere, and an installer wouldn't need to pay VAT.
Modelling was done using homeW57.yaml specification.
Radiators for 57°C radiator temperature | ||||||
---|---|---|---|---|---|---|
Room | Heat loss W | Rated power needed | Existing radiators | Possible radiators | Price £ | Room Temp |
Lounge 21°C | 1589 | 2441 | T21 600x600 833W | K2 1800x600 2376(1547)W |
371 |
20.9 |
Dining room 21°C | 616 | 946 | T21 600x600 833W | K2 600x600 1039(676)W | 97 | 21.0 |
Back room 21°C | 884 | 1358 | T11 600x900 923W | K2 600x800 1385(902)W | 118 | 21.0 |
Front bedroom 18°C | 283 | 391 | T11 400x700 460W | [K1 400x700 460(279)W] | 0 | 18.0 |
Back bedroom 18°C | 133 | 184 | T11 400x700 460W | [K1 400x700 460(279)W] | 0 | 18.0 |
Ensuite 21°C | 231 | 355 | Towel 150W | [(150W)] | 0 | 18.5 |
Hall 21°C | 585 | 899 | T21 500x700 972W | [T21 500x700 972(633)W] | 0 | 21.2 |
Study 21°C | 471 | 724 | T11 600x400 410W | K2
700x400 784(510)W |
98 | 21.0 |
Bathroom 21°C | 309 | 475 | Towel 1200x600 415W | P+ 600x400 539(351)W | 63 | 21.0 |
Total |
5101 |
|
|
5399 = 106% | 747 |
|
With these radiators, a radiator temperature of 48°C (flow temperature of 51°C) would be needed for an outside temperature of 7°C.
5 new radiators are needed, at a cost of £747, compared to 6 new radiators at a cost of £912 if we used a 55°C flow temperature.
A compromise might be to use the existing hall radiator and change the other 5 radiators to the 55°C flow specification. This would cost £806, i.e. £59 more than the 60°C flow specification, but £106 less than changing all 6 radiators. The hall radiator could be upgraded later if required.
The performance of this compromise would be:
Radiators for 52°C radiator temperature, original hall radiator | |||||||
---|---|---|---|---|---|---|---|
Room | Heat loss W | Rated power needed | Existing radiators | Possible radiators | Price £ | Room Temp @ 55°C flow |
Room Temp @ 60°C flow |
Lounge 21°C | 1589 | 2976 | T21 600x600 833W | K2 1800x600 2376(1269)W |
371 |
20.4 | 20.9 |
Dining room 21°C | 616 | 1154 | T21 600x600 833W | K2 600x900 1558(832)W | 121 | 20.9 | 21.0 |
Back room 21°C | 884 | 1655 | T11 600x900 923W | K2 700x900 1764(942)W | 140 | 21.0 | 21.0 |
Front bedroom 18°C | 283 | 467 | T11 400x700 460W | [K1 400x700 460(279)W] | 0 | 17.6 | 18.0 |
Back bedroom 18°C | 133 | 219 | T11 400x700 460W | [K1 400x700 460(279)W] | 0 | 18.0 | 18.0 |
Ensuite 21°C | 231 | 433 | Towel 150W | [(150W)] | 0 | 18.5 | 18.5 |
Hall 21°C | 585 | 1096 | T21 500x700 972W | [T21 500x700 972(519)W] | 0 | 20.2 | 21.2 |
Study 21°C | 471 | 882 | T11 600x400 410W | K2
700x400 784(419)W |
98 | 20.0 | 21.0 |
Bathroom 21°C | 309 | 577 | Towel 1200x600 415W | K2 600x400 693(370)W | 76 | 21.0 | 21.0 |
Total |
5101 |
|
|
5059 = 99% | 806 |
|
|
At 55°C flow, the lounge would be 0.2°C cooler and the study would be 0.1°C cooler than if the hall radiator was replaced. These differences would probably not be noticeable. The hall would be 0.9°C cooler.
At 60°C flow, the temperatues would be unchanged by not replacing the hall radiator.
With these radiators, a radiator temperature of 53°C (flow temperature of 56°C) would be needed for an outside temperature of 7°C.
Written Sep 2023.
I am assuming a flow temperaure of 65°C and return temperature of 59°C, hence a radiator temperature of 62°C. This could be for the existing gas boiler (or a replacement boiler), or possibly for the Vaillant Arotherm plus heat pump.
For a room temperature of 21°C, ΔT will be 41°C and correction
factor will be 0.771.
For a room temperature of 18°C, ΔT will be 44°C and correction
factor will be 0.846.
Prices are from Stelrad website, including VAT. They could probably be bought cheaper elsewhere, and an installer wouldn't need to pay VAT.
Modelling was done using home W65.yaml specification.
Radiators for 62°C radiator temperature | ||||||
---|---|---|---|---|---|---|
Room | Heat loss W | Rated power needed W | Existing radiators | Possible radiators | Price £ | Room Temp °C |
Lounge 21°C | 1589 | 2061 | T21 600x600 833W | K2 1800x600 2376(1269)W |
371 |
21.0 |
Dining room 21°C | 616 | 799 | T21 600x600 833W | [T21 600x600 833(811)W] | 0 | 21.0 |
Back room 21°C | 884 | 1147 | T11 600x900 923W | K2 600x900 1572(1212)W | 98 | 21.0 |
Front bedroom 18°C | 283 | 335 | T11 400x700 460W | [T11 400x700 460(484)W] | 0 | 18.0 |
Back bedroom 18°C | 133 | 157 | T11 400x700 460W | [T11 400x700 460(484)W] | 0 | 18.0 |
Ensuite 21°C | 231 | 300 | Towel 150W | [(150W)] | 0 | 18.5 |
Hall 21°C | 585 | 759 | T21 500x700 972W | [T21 500x700 972(947)W] | 0 | 21.0 |
Study 21°C | 471 | 611 | T11 600x400 410W | K2 600x400 699(539)W | 46 | 21.0 |
Bathroom 21°C | 309 | 401 | Towel 1200x600 415W | [T11
600x400 410(316)W] re-used from study |
0 | 21.0 |
Total |
5101 |
|
|
5427 = 106% | 557 |
|
With these radiators, the table below shows the heating powers and radiator temperatures needed for the specified outside temperatures. The radiator temperature is based on the lounge radiator, which is the main limiting radiator. Flow temperatures for a heat pump would typically be about 3°C higher than the radiator temperature.
Outside temperature °C | Power needed W | Radiator temperature °C |
---|---|---|
-7 | 6119 | 64 |
-5 | 5655 | 61 |
-2 | 5104 | 59 |
0 | 4703 | 56 |
2 | 4298 | 55 |
3 | 4096 | 54 |
5 | 3691 | 52 |
7 | 3301 | 50 |
10 | 2710 | 46 |
12 | 2337 | 43 |
15 | 1765 | 39 |
Written Sep 2023.
I am assuming a flow temperaure of 75°C and return temperature of 65°C, hence a radiator temperature of 70°C. This could be for the existing gas boiler (or a replacement boiler), or possibly for the Vaillant Arotherm plus heat pump.
For a room temperature of 21°C, ΔT will be 49°C and correction
factor will be 0.974.
For a room temperature of 18°C, ΔT will be 52°C and correction
factor will be 1.052.
Prices are from Stelrad website, including VAT. They could probably be bought cheaper elsewhere, and an installer wouldn't need to pay VAT.
Modelling was done using home W70.yaml specification.
Radiators for 70°C radiator temperature | ||||||
---|---|---|---|---|---|---|
Room | Heat loss W | Rated power needed W | Existing radiators | Possible radiators | Price £ | Room Temp °C |
Lounge 21°C | 1589 | 1631 | T21 600x600 833W | K2 1800x600 2376(1269)W |
371 |
21.0 |
Dining room 21°C | 616 | 632 | T21 600x600 833W | [T21 600x600 833(811)W] | 0 | 21.0 |
Back room 21°C | 884 | 908 | T11 600x900 923W | [T11 600x900 923(899)W] | 0 | 21.0 |
Front bedroom 18°C | 283 | 269 | T11 400x700 460W | [T11 400x700 460(484)W] | 0 | 18.0 |
Back bedroom 18°C | 133 | 126 | T11 400x700 460W | [T11 400x700 460(484)W] | 0 | 18.0 |
Ensuite 21°C | 231 | 237 | Towel 150W | [(150W)] | 0 | 18.5 |
Hall 21°C | 585 | 601 | T21 500x700 972W | [T21 500x700 972(947)W] | 0 | 21.0 |
Study 21°C | 471 | 484 | T11 600x400 410W | T11 700x400 438(468)W | 40 | 20.1 |
Bathroom 21°C | 309 | 317 | Towel 1200x600 415W | [T11
600x400 410(399)W] re-used from study |
0 | 21.0 |
Total |
5101 |
|
|
5427 = 106% | 411 |
|
With these radiators, a radiator temperature of 58°C (flow temperature of 61°C) would be needed for an outside temperature of 7°C.
Octopus are sizing radiators assuming a flow temperature of 45°C.
The actual correction factors used by Octopus are 0.324 for a room temperature of 21°C and 0.386 for a room temperature of 18°C. These correspond to ΔT of 21.0°C and 24.0°C respectively, and hence to a radiator water temperature of 42.0°C in both cases.
Octopus specified radiators:
Room | Description | Design room temp °C | Correction for low delta | Room heat loss W | Specified radiator output W at design temps | Specified radiator output W at ΔT 50°C | Correction factor for low ΔT | Required radiator output W at ΔT 50°C | Price inc VAT £ |
---|---|---|---|---|---|---|---|---|---|
Lounge | K2 Vert Radiator - H1800mm x L600mm | 21.0 | 0.341 | 1993 | 773 | 2376 | 0.325 | 6151 | 371 |
Lounge | K3 Radiator - H700mm x L1400mm | 21.0 | 0.341 | 1993 | 1225 | 3797 | 0.323 |
|
459? |
Back room | K3 Radiator - H700mm x L1400mm | 21.0 | 0.341 | 1134 | 1225 | 3797 | 0.323 | 3500 | 459? |
Hall | K2 Radiator - H600mm x L600mm | 18.0 | 0.402 | 352 | 398 | 1039 | 0.383 | 912 | 92 |
Study | K2 Radiator - H600mm x L400mm | 18.0 | 0.402 | 270 | 261 | 693 | 0.377 | 699 | 71 |
Front bedroom | K2 Radiator - H450mm x L1400mm | 18.0 | 0.402 | 687 | 758 | 1919 | 0.395 | 1780 | 173 |
Back bedroom | K2 Radiator - H450mm x L900mm | 18.0 | 0.402 | 493 | 483 | 1234 | 0.391 | 1227 | 105 |
Ensuite | 21.0 |
|
531 |
|
|
|
|
|
|
Bathroom | 22.0 |
|
396 |
|
|
|
|
|
|
Total |
|
|
1730 |
This is my attempt to size radiators and choose the flow temperature using the MCS Heat Emitter Guide (section 4 of MGD-007 Reference Data and Tools).
The guide uses an "Oversize Factor" (radiator rated output divided room heat loss) to look up the required flow temperature (or equivalently "star rating") using a graph. The graph corresponds to the first two columns in the following table:
Oversize factor | Flow temperature | Correction factor | ΔT | Room temperature |
---|---|---|---|---|
1.0 |
|
1.0 | 50 |
|
1.6 | 60 | 0.63 | 35 | 25 |
1.9 | 55 | 0.53 | 31 | 24 |
2.4 | 50 | 0.42 | 26 | 24 |
3.1 | 45 | 0.32 | 21 | 24 |
4.3 | 40 | 0.23 | 16 | 24 |
6.8 | 35 | 0.15 | 12 | 23 |
The third column is simply the reciprocal of the first column, and corresponds to the "Operating factor" in the Stelrad radiator temperature table. The fourth column is the difference between radiator temperature and room temperature, obtained by interpolating in the Stelrad table. The fifth column is the difference between the second and fourth columns.
Note that flow temperature is not the same as radiator temperature, since there is a temperature drop across the radiator. My guess is that MCS are assuming a room temperature of 20°C and a drop across the radiators of 8°C (although it could equally well be 21°C and 6°C respectively).
The first two columns can be approximated by:
FT = 27.8 + 52.3 / OF
Analysis of existing radiators:
Room | Heat loss | Radiator sizes | Radiator output at ΔT 50°C | Oversize factor | Required flow temperature |
---|---|---|---|---|---|
Lounge | 1993 | P+
600x600 P+ 600x600 |
1616 | 0.81 | 92 |
Back room | 1134 | K1 600x900 | 882 | 0.78 | 95 |
Front bedroom | 687 | K1 400x700 | 470 | 0.68 | 105 |
Back bedroom | 493 | K1 400x700 | 470 | 0.95 | 83 |
Hall | 352 | P+ 500x700 | 821 | 2.33 | 50 |
Study | 270 | K1 600x400 | 392 | 1.45 | 64 |
Bathroom | 396 | Towel 1200x600 | 415/616 | 1.04/1.56 | 78/61 |
Ensuite | 531 | Towel 700x400 |
|
|
|
The alternative output of 616W for the bathroom towel radiator is if we painted it white.
Analysis using 4.5 Guidance Table:
Room | Heat loss | Floor area | Specific heat loss | Guidance for 46-50°C flow | Oversize factor for 46-50°C flow | Guidance for 51-55°C flow | Oversize factor for 51-55°C flow |
---|---|---|---|---|---|---|---|
Lounge | 1993 | 22.9 | 87 | Go ahead | 2.4 | Caution | 1.9 |
Back room | 1134 | 13.7 | 83 | Go ahead | 2.4 | Caution | 1.9 |
Front bedroom | 687 | 11.2 | 61 | Go ahead | 2.4 | Caution | 1.9 |
Back bedroom | 493 | 10.5 | 47 | Go ahead | 2.4 | Caution | 1.9 |
Hall | 352 | 3.1 | 114 | Caution | 2.4 | Caution | 1.9 |
Study | 270 | 2.7 | 100 | Caution | 2.4 | Caution | 1.9 |
Bathroom | 396 | 3.2 | 124 | Caution | 2.4 | Caution | 1.9 |
Ensuite | 531 | 4.7 | 113 | Caution | 2.4 | Caution | 1.9 |
The guidance in the MCS table is always "Caution" for flow
temperatures of 51°C and above. The guidance for 46-50°C flow
changes from "Go ahead" to "Caution" when the specific heat loss is
100 or above.
"Caution" means: "System can perform at these design conditions
with extra consideration on the emitter and heat pump design sought
from the specialist designer/manufacturer."
An "oversize factor" of 2.4 corresponds to a radiator correction
factor 1/2.4 = 0.42.
An "oversize factor" of 1.9 corresponds to a radiator correction
factor 1/1.9 = 0.53.
In my radiator design above, I am using correction factors in the
range 0.43 to 0.49 for a flow temperature of 50°C, and 0.53 to 0.61
for a flow temperature of 55°C. The ranges are to cover varying
target room temperatures.