Name | Country | Price £ | Heating power kW | Rated input kW A |
COP | Energy rating | Air flow m³/h | Noise pressure at 1m / power dB(A) | Refrigerant | Dimensions mm | Weight kg | WiFi App |
---|---|---|---|---|---|---|---|---|---|---|---|---|
Powrmatic Vision Compact 2.3DW | UK | 1500 | 1.71 0.75-2.4 |
0.54 |
3.15 | A+ | 27-39/56 | R290 | 810 | 38 | InnovApp | |
Trotec PAC-W 2600 SH | 1050 | 2.3 | 0.65 |
3.1 | A+ | 500 | ?-48/59 | R290 | 1000x585x205 | 38 | InnovApp | |
electriQ IQOOL-SMART12HP | 750 | 2.35 | 0.745 | 3.15 |
A | 500 | -/58 | R290 | 1000x585x205 | 38 | Tuya Smart | |
electriQ IQOOL-SMART15HP | 800 | 2.93 | 0.815 4.0 |
3.60 |
A+ | 500 | -/61 | R290 | 1000x585x205 | 39 | Tuya Smart | |
BLU (ebay) | 900 | 2.93 | 0.945 | 3.1 | 520 | R290 | 1000x585x205 | 43.5 | ||||
Qlima WDH229 | 1130 | 2.35 0.7-2.962 |
0.745 3.2 |
3.1 | A | 350 450 500 | 30-?/58 | R290 | 1000x575x205 | 42 | Tuya Smart Life | |
Argo Apollo | Italy | 995 | 2.36 1.0-2.80 |
0.76 | 3.11 |
A | 480 | 29/56 | R32 | 965 | 36 | |
Unico Air 8HP | Italy | 960 | 1.7 | 3.1 | A | 27-38/53 | R410A | 978 | 37 | |||
Unico Air 25HP | Italy | 1610 | 2.1@7/20°C 1.9-2.4 |
0.7 7/20°C |
3.1 7/20°C |
A 7/20°C |
27-38/53 | R32 | 978 | 39 |
The fixing bracket holes for the Electriq are approximately 56mm below the top of the unit (based on this image of the installation template, which doesn't ppear to be to scale!). There appears to be a horizontal timber extending about 30mm below the plastic strip under the lounge side window. If we want to hang the heat pump from this horizontal timber, we would have to add an extra horizontal timber below it, with thickness around 2*(56-30) = 52mm (so the screws would go roughly in the middle of the added timber. We would have to remove part of the panel (or possibly a cladding plank) to install the additional timber.
Average winter temperature at Odiham is about 8°C.
This assumes heaters with adequate power in all rooms, providing 20°C in living rooms and bathroom, 18°C in bedrooms, kitchen and hall.
Outside temperature °C | -5 | -2 | 2 | 7 | 10 | 15 |
Dining room | 679 | 607 | 511 | 392 | 320 | 187 |
Lounge | 1950 | 1780 | 1555 | 1273 | 1103 | 633 |
Back Room | 899 | 809 | 689 | 539 | 449 | 274 |
Front Bedroom | 496 | 396 | 264 | 98 | 0 | 0 |
Back Bedroom | 516 | 414 | 277 | 107 | 5 | 0 |
Study | 755 | 674 | 567 | 432 | 351 | 197 |
Bathroom | 311 | 282 | 244 | 195 | 166 | 102 |
Hall | 0 | 0 |
0 |
0 |
0 |
0 |
Kitchen | 0 | 0 | 0 | 0 | 0 | 0 |
Total |
5605 | 4963 |
4107 | 3036 | 2394 | 1393 |
Power requirement is 210W/°C for outside temperatures in range -5°C to 10°C.
NEEDS UPDATING
Outside temperature °C | -5 | -2 | 2 | 7 | 10 | 15 |
Dining room | 1220 | 869 |
603 |
446 | ||
Lounge | 1570 | 1760 |
1592 |
1256 | ||
Back Room | 913 | 805 |
666 |
503 | ||
Front Bedroom | 340 | 328 |
317 |
174 | ||
Back Bedroom | 340 | 328 |
317 |
185 | ||
Study | 265 | 256 |
245 |
181 | ||
Bathroom | 162 | 140 |
113 |
88 | ||
Hall | 206 | 24 |
0 |
0 | ||
Total |
5014 | 4508 |
3853 |
2831 | ||
% from heat pumps | 74 |
76 |
74 |
78 |
||
Total power from other heaters | 1311 |
1074 |
992 |
627 |
||
Total input power | 3261 | 2673 | 2088 | 1236 | ||
COP | 1.54 | 1.69 | 1.85 | 2.29 |
Outside temperature °C | -5 | -2 | 2 | 7 | 10 | 15 |
Back Bedroom | 16.3 | 16.7 |
17.7 |
17.9 | ||
Back Room | 20.9 | 20.0 |
20.0 |
20.0 | ||
Bathroom | 20.9 | 19.9 |
20.0 |
20.0 | ||
Dining Room | 20.8 | 20.0 |
20.0 |
20.0 | ||
Front Bedroom | 16.4 | 16.8 |
17.7 |
17.9 | ||
Hall | 18.0 | 18.0 |
18.5 |
18.8 | ||
Inner Hall | 18.6 | 18.5 |
18.9 |
19.2 | ||
Kitchen | 17.9 | 17.9 |
18.4 |
18.7 | ||
Landing | 17.5 | 17.7 |
18.3 |
18.6 | ||
Lounge | 19.8 | 19.7 |
19.9 |
20.0 | ||
Study | 18.1 | 18.6 |
19.9 |
19.9 |
An outside temperature of 7°C is about average for the winter, and COPs measured at 7°C tend to be similar to SCOPs. So the total heating for the winter should be around 2.831*24*90 = 6115kWh, and the total input power should be about 1236*24*90 = 2670kWh. At 35p/kWh, the cost using resistive heating would be 6115*35/100 = £2140, and the cost using A2A heat pumps would be 2670*35/100 = £935 - a saving of 2140-935 = £1200.
At 7°C, power from heaters other than the heat pumps is 627 W. If this could be provided by a A2W heat pump, the input power would be reduced to about 627/3 = 299 W, a reduction of 418W = 418/1236*100 = 34%.
Heat pumps in lounge, dining room, and back room. Portable heater in study.
Outside temperature °C | -5 | -2 | 0 | 2 | 7 | 10 | 15 |
Dining room | 1572 | 1294 | 950 | 584 | 413 | 330 |
|
Lounge | 1632 | 1790 | 1945 | 2127 | 1615 | 1285 |
|
Back Room | 1411 | 1151 | 1025 | 896 | 675 | 547 |
|
Study | 417 | 364 | 332 | 299 | 222 | 175 |
|
Total output power |
5033 | 4600 | 4252 | 3905 | 2925 | 2337 |
|
% from heat pumps | 92 | 92 | 92 | 92 | 92 | 92 |
|
Total power from other heaters | 417 | 364 | 332 | 299 | 222 | 175 |
|
Total input power | 2800 | 2327 | 1989 | 1682 | 973 | 776 |
|
COP | 1.80 | 1.98 | 2.14 | 2.32 | 3.01 | 3.01 |
Outside temperature °C | -5 | -2 | 2 | 7 | 10 | 15 |
Back Bedroom | 13.7 | 14.9 | 16.2 | 17.2 | 17.9 |
|
Back Room | 20.0 | 20.0 | 20.0 | 20.0 | 20.0 |
|
Bathroom | 17.2 | 17.9 | 18.4 | 18.8 | 19.0 |
|
Dining Room | 19.2 | 20.0 | 20.0 | 20.0 | 20.0 |
|
Front Bedroom | 14.4 | 15.0 | 16.2 | 17.3 | 17.9 |
|
Hall | 15.9 | 17.0 | 17.9 | 18.4 | 18.8 |
|
Inner Hall | 17.8 | 18.4 | 18.9 | 19.2 | 19.3 |
|
Kitchen | 16.3 | 17.4 | 18.2 | 18.7 | 18.9 |
|
Landing | 15.5 | 16.6 | 17.6 | 18.3 | 18.7 |
|
Lounge | 18.3 | 19.3 | 20.0 | 20.0 | 20.0 |
|
Study | 20.0 | 20.0 | 20.0 | 20.0 | 20.0 |
Heat pumps in lounge, dining room, and back room. Portable heaters in study and bedrooms.
Outside temperature °C | -5 | -2 | 2 | 7 | 10 | 15 |
Dining room | 1572 | 1294 | 584 | 413 | 330 |
|
Lounge | 1632 | 1790 | 2127 | 1615 | 1285 |
|
Back Room | 1411 | 1151 | 896 | 675 | 547 |
|
Study | 417 | 364 | 299 | 222 | 175 |
|
Total output power |
5033 | 4600 | 3905 | 2925 | 2337 |
|
% from heat pumps | 92 | 92 | 92 | 92 | 92 |
|
Total power from other heaters | 417 | 364 | 299 | 222 | 175 |
|
Total input power | 2800 | 2327 | 1682 | 973 | 776 |
|
COP | 1.80 | 1.98 | 2.32 | 3.01 | 3.01 |
Outside temperature °C | -5 | -2 | 2 | 7 | 10 | 15 |
Back Bedroom | 13.7 | 14.9 | 16.2 | 17.2 | 17.9 |
|
Back Room | 20.0 | 20.0 | 20.0 | 20.0 | 20.0 |
|
Bathroom | 17.2 | 17.9 | 18.4 | 18.8 | 19.0 |
|
Dining Room | 19.2 | 20.0 | 20.0 | 20.0 | 20.0 |
|
Front Bedroom | 14.4 | 15.0 | 16.2 | 17.3 | 17.9 |
|
Hall | 15.9 | 17.0 | 17.9 | 18.4 | 18.8 |
|
Inner Hall | 17.8 | 18.4 | 18.9 | 19.2 | 19.3 |
|
Kitchen | 16.3 | 17.4 | 18.2 | 18.7 | 18.9 |
|
Landing | 15.5 | 16.6 | 17.6 | 18.3 | 18.7 |
|
Lounge | 18.3 | 19.3 | 20.0 | 20.0 | 20.0 |
|
Study | 20.0 | 20.0 | 20.0 | 20.0 | 20.0 |
Heat pumps in lounge, dining room, and back room. Portable heater in study. Portable heater in lounge to supplement heat pump in very cold weather.
Outside temperature °C | -5 | -2 | 2 | 7 | 10 | 15 |
Dining room | 903 | 822 | 539 | 404 | 323 | |
Lounge | 1540 | 1751 | 1967 | 1464 | 1165 | |
Back Room | 1170 | 1045 | 861 | 653 | 528 | |
Study | 859 | 763 | 617 | 457 | 362 | |
Lounge PE | 872 | 360 | 0 | 0 | 0 | |
Total output power |
5343 | 4741 | 3984 | 2978 | 2379 | |
% from heat pumps | 68 | 76 | 85 | 85 | 85 | |
Total power from other heaters | 1731 | 1123 | 617 | 457 | 362 | |
Total input power | 3561 | 2841 | 1910 | 1158 | 992 | |
COP | 1.46 | 1.68 | 2.09 | 2.57 | 2.58 |
Outside temperature °C | -5 | -2 | 2 | 7 | 10 | 15 |
Back Bedroom | 14.8 | 15.4 | 16.3 | 17.3 | 17.9 | |
Back Room | 20.0 | 20.0 | 20.0 | 20.0 | 20.0 | |
Bathroom | 18.0 | 18.2 | 18.5 | 18.9 | 19.1 | |
Dining Room | 20.0 | 20.0 | 20.0 | 20.0 | 20.0 | |
Front Bedroom | 14.9 | 15.5 | 16.4 | 17.4 | 18.0 | |
Hall | 18.4 | 18.6 | 18.9 | 19.2 | 19.4 | |
Inner Hall | 18.6 | 18.7 | 19.0 | 19.2 | 19.4 | |
Kitchen | 17.7 | 17.9 | 18.4 | 18.8 | 19.0 | |
Landing | 16.8 | 17.2 | 17.8 | 18.4 | 18.7 | |
Lounge | 19.8 | 19.8 | 20.0 | 20.0 | 20.0 | |
Study | 20.0 | 20.0 | 20.0 | 20.0 | 20.0 |
Input power requirement is 114W/ °C for temperature range 2°C to 10°C.
Input power requirement is 236W/ °C for temperature range -5°C to 2°C.
Heat pumps in lounge and back room, portable electric heaters in dining room and study (no heating in other rooms).
Outside temperature °C | -5 | -2 | 2 | 7 | 10 | 15 |
Dining room | 1000 | 456 | 373 | |||
Lounge | 2167 | 2054 | 1722 | |||
Back Room | 1110 | 822 | 691 | |||
Study | 311 | 231 | 184 | |||
Total output power |
4588 | 3562 | 2970 | |||
% from heat pumps | 71 | 81 | 81 | |||
Total power from other heaters | 1311 | 687 | 557 | |||
Total input power | 2552 | 1485 | 1227 | |||
COP | 1.80 | 2.40 | 2.42 |
Input energy requirement is 162W/°C for outside temperatures in range 2°C to 10°C.
Outside temperature °C | -5 | -2 | 2 | 7 | 10 | 15 |
Back Bedroom | 15.2 | 16.5 |
17.1 | |||
Back Room | 20.0 | 20.0 |
20.0 | |||
Bathroom | 17.8 | 18.4 |
18.6 | |||
Dining Room | 20.0 | 20.0 |
20.0 | |||
Front Bedroom | 15.1 | 16.5 |
17.1 | |||
Hall | 17.3 | 18.1 |
19.1 | |||
Inner Hall | 18.4 | 18.9 |
19.1 | |||
Kitchen | 17.4 | 18.2 |
18.5 | |||
Landing | 16.8 | 17.7 |
18.1 | |||
Lounge | 19.6 | 20.0 |
20.0 | |||
Study | 20.0 | 20.0 |
20.0 |
Two heat pumps in lounge, portable electric heaters in back room and study (no heating in other rooms).
Outside temperature °C | -5 | -2 | 2 | 7 | 10 | 15 |
Dining room | 748 | 433 | 352 | |||
Lounge | 2140 | 1791 | 1491 | |||
Back Room | 1027 | 775 | 648 | |||
Study | 685 | 498 | 402 | |||
Total output power |
4600 | 3498 | 2893 | |||
% from heat pumps | 63 | 64 | 64 | |||
Total power from other heaters | 1712 | 1273 | 1051 | |||
Total input power | 2814 | 1891 | 1563 | |||
COP | 1.63 | 1.85 | 1.85 |
Input energy requirement is 156W/°C for outside temperatures in range 2°C to 10°C.
Outside temperature °C | -5 | -2 | 2 | 7 | 10 | 15 |
Back Bedroom | 15.6 | 16.7 |
17.3 | |||
Back Room | 20.0 | 20.0 |
20.0 | |||
Bathroom | 18.1 | 18.6 |
18.8 | |||
Dining Room | 20.0 | 20.0 |
20.0 | |||
Front Bedroom | 15.5 | 16.7 |
17.3 | |||
Hall | 18.7 | 19.1 |
19.3 | |||
Inner Hall | 18.7 | 19.0 |
19.2 | |||
Kitchen | 17.9 | 18.4 |
18.7 | |||
Landing | 17.2 | 18.0 |
18.3 | |||
Lounge | 19.8 | 20.0 |
20.0 | |||
Study | 20.0 | 20.0 |
20.0 |
NEEDS DOORS OPENING
Heat pumps in lounge and back room, portable electric heaters in dining room and study. Portable heater in lounge to supplement heat pump in very cold weather.
Outside temperature °C | -5 | -2 | 2 | 7 | 10 | 15 |
Dining room | 931 |
847 |
671 | 418 | 334 | |
Lounge | 1540 |
1751 |
2137 | 1699 | 1351 | |
Back Room | 911 |
813 |
681 | 516 | 418 | |
Study | 436 |
387 |
321 | 238 | 189 | |
Lounge PE | 1329 | 769 | 0 | 0 | 0 | |
Total output power |
5146 |
4567 |
3810 | 2870 | 2292 | |
% from heat pumps | 48 |
56 |
74 | 77 | 77 | |
Total power from other heaters | 2696 |
2002 |
992 | 656 | 523 | |
Total input power | 3997 |
3199 |
2069 | 1271 | 1015 | |
COP | 1.29 |
1.43 |
1.84 | 2.26 | 2.26 |
Outside temperature °C | -5 | -2 | 2 | 7 | 10 | 15 |
Back Bedroom | 14.4 |
15.1 |
16.0 | 17.1 | 17.8 | |
Back Room | 20.0 |
20.0 |
20.0 | 20.0 | 20.0 | |
Bathroom | 12.2 |
13.0 |
14.1 | 15.5 | 16.4 | |
Dining Room | 20.0 |
20.0 |
20.0 | 20.0 | 20.0 | |
Front Bedroom | 14.6 |
15.2 |
16.1 | 17.2 | 17.8 | |
Hall | 16.9 |
17.2 |
17.7 | 18.4 | 18.7 | |
Inner Hall | 17.8 |
18.1 |
18.4 | 18.9 | 19.1 | |
Kitchen | 17.4 |
17.6 |
18.1 | 18.6 | 18.9 | |
Landing | 16.5 |
16.9 |
17.4 | 18.2 | 18.6 | |
Lounge | 19.8 |
19.8 |
19.9 | 20.0 | 20.0 | |
Study | 20.0 |
20.0 |
20.0 | 20.0 | 20.0 |
Input power requirement is 132W/ °C for temperature range 2°C to 10°C.
Input power requirement is 275W/ °C for temperature range -5°C to 2°C.
Heat pump in lounge. Portable electric heaters in dining room, back room, and study.
Outside temperature °C | -5 | -2 | 2 | 7 | 10 | 15 |
Dining room | 1719 |
523 | 226 | 143 | ||
Lounge | 1605 |
2143 | 1794 | 1464 | ||
Back Room | 1353 |
915 | 677 | 548 | ||
Study | 414 |
300 | 222 | 175 | ||
Total output power |
5091 |
3880 | 2919 | 2331 | ||
% from heat pumps | 32 |
55 | 61 | 63 | ||
Total power from other heaters | 3486 |
1738 | 1125 | 867 | ||
Total input power | 5091 |
2553 | 1623 | 1274 | ||
COP | 1.18 |
1.52 | 1.80 | 1.83 |
Outside temperature °C | -5 | -2 | 2 | 7 | 10 | 15 |
Back Bedroom | 14.0 |
16.1 | 17.2 | 17.8 | ||
Back Room | 20.0 |
20.0 | 20.0 | 20.0 | ||
Bathroom | 17.4 |
18.4 | 18.8 | 19.0 | ||
Dining Room | 19.8 |
19.8 | 20.0 | 19.8 | ||
Front Bedroom | 14.0 |
16.1 | 17.3 | 17.9 | ||
Hall | 16.2 |
17.8 | 18.4 | 18.8 | ||
Inner Hall | 18.0 |
18.8 | 19.2 | 19.3 | ||
Kitchen | 16.7 |
18.1 | 18.7 | 18.9 | ||
Landing | 15.8 |
17.5 | 18.3 | 18.6 | ||
Lounge | 18.7 |
19.8 | 20.0 | 20.0 | ||
Study | 20.0 |
20.0 | 20.0 | 20.0 |
Heat pump in lounge. Portable electric heaters in dining room, back room, and study. Portable heater in lounge to supplement heat pump in very cold weather.
Outside temperature °C | -5 | -2 | 2 | 7 | 10 | 15 |
Dining room | 903 | 822 | 539 | 404 | 323 | |
Lounge | 1540 | 1751 | 1967 | 1464 | 1165 | |
Back Room | 1170 | 1045 | 861 | 652 | 528 | |
Study | 859 | 763 | 617 | 457 | 362 | |
Lounge PE | 872 | 359 | 0 | 0 | 0 | |
Total output power |
5344 | 4741 | 3984 | 2978 | 2379 | |
% from heat pumps | 29 | 37 | 49 | 49 | 49 | |
Total power from other heaters | 3804 | 2990 | 2017 | 1514 | 1213 | |
Total input power | 4619 | 3805 | 2772 | 1920 | 1537 | |
COP | 1.16 | 1.25 | 1.44 | 1.55 | 1.55 |
Outside temperature °C | -5 | -2 | 2 | 7 | 10 | 15 |
Back Bedroom | 14.8 | 15.4 | 16.3 | 17.3 | 17.9 | |
Back Room | 20.0 | 20.0 | 20.0 | 20.0 | 20.0 | |
Bathroom | 18.0 | 18.2 | 18.5 | 18.9 | 19.1 | |
Dining Room | 20.0 | 20.0 | 20.0 | 20.0 | 20.0 | |
Front Bedroom | 14.9 | 15.5 | 16.4 | 17.4 | 18.0 | |
Hall | 18.4 | 18.6 | 18.9 | 19.2 | 19.4 | |
Inner Hall | 18.6 | 18.7 | 19.0 | 19.2 | 19.4 | |
Kitchen | 17.7 | 17.9 | 18.4 | 18.8 | 19.0 | |
Landing | 16.8 | 17.2 | 17.8 | 18.4 | 18.7 | |
Lounge | 19.8 | 19.8 | 20.0 | 20.0 | 20.0 | |
Study | 20.0 | 20.0 | 20.0 | 20.0 | 20.0 |
Input power requirement is 154W/ °C for temperature range 2°C to 10°C.
Input power requirement is 264W/ °C for temperature range -5°C to 2°C.
NEEDS DOORS OPENING
Outside temperature °C | -5 | -2 | 2 | 7 | 10 | 15 |
Dining room | 1653 | 1294 | 794 | 418 | 334 |
|
Lounge | 2000 | 2000 | 2000 | 1697 | 1350 |
|
Back Room | 932 | 828 | 686 | 516 | 418 |
|
Study | 441 | 390 | 322 | 238 | 189 |
|
Total |
5026 | 4512 | 3802 | 2868 | 2292 |
Energy requirement is 183kWh/°C for outside temperatures in range 2°C to 10°C.
Outside temperature °C | -5 | -2 | 2 | 7 | 10 | 15 |
Back Bedroom | 13.9 | 14.7 | 15.9 | 17.1 | 17.8 |
|
Back Room | 20.0 | 20.0 | 20.0 | 20.0 | 20.0 |
|
Bathroom | 11.9 | 12.8 | 14.1 | 15.5 | 16.4 |
|
Dining Room | 20.0 | 20.0 | 20.0 | 20.0 | 20.0 |
|
Front Bedroom | 14.0 | 14.8 | 16.0 | 17.2 | 17.8 |
|
Hall | 16.3 | 16.8 | 17.6 | 18.4 | 18.7 |
|
Inner Hall | 17.2 | 17.6 | 18.3 | 18.9 | 19.1 |
|
Kitchen | 16.7 | 17.2 | 17.9 | 18.6 | 18.9 |
|
Landing | 15.9 | 16.6 | 17.3 | 18.2 | 18.6 |
|
Lounge | 19.0 | 19.3 | 19.7 | 20.0 | 20.0 |
|
Study | 20.0 | 20.0 | 20.0 | 20.0 | 20.0 |
NEEDS UPDATING
Used to determine radiator sizes for rooms that don't have heat pumps.
Is also relevant if we were to use portable electric heaters in all rooms that don't have heat pumps.
Outside temperature °C | -5 | -2 | 2 | 3 | 5 | 7 | 10 | 15 |
Dining room | 1210 | 1177 |
656 |
440 |
||||
Lounge | 1579 | 1772 |
2124 |
1725 |
||||
Back Room | 1023 | 815 |
693 |
528 |
||||
Front Bedroom | 857 | 611 |
424 |
205 |
||||
Back Bedroom | 881 | 604 |
417 |
203 |
||||
Study | 398 | 356 |
297 |
221 |
||||
Bathroom | 238 | 134 |
197 |
150 |
||||
Hall | 298 | 174 |
26 |
0 |
||||
Total |
6484 |
5739 |
4835 |
3471 |
||||
% from heat pumps | 59 |
66 |
72 |
78 |
||||
Total power from other heaters | 2671 |
1975 |
1362 |
778 |
||||
Total input power | 4663 | 3726 | 2695 | 1526 |
||||
COP | 1.39 | 1.54 | 1.79 | 2.28 |
Outside temperature °C | -5 | -2 | 2 | 3 | 5 | 7 | 10 | 15 |
Back Bedroom | 18.0 | 18.0 |
18.0 |
18.0 |
||||
Back Room | 19.7 | 20.0 |
20.0 |
20.0 |
||||
Bathroom | 20.0 | 20.0 |
20.0 |
20.0 |
||||
Dining Room | 19.6 | 20.0 |
20.0 |
20.0 |
||||
Front Bedroom | 18.0 | 18.0 |
18.0 |
18.0 |
||||
Hall | 18.0 | 18.0 |
18.0 |
18.4 |
||||
Inner Hall | 18.1 | 18.2 |
18.6 |
18.9 |
||||
Kitchen | 17.2 | 17.5 |
18.0 |
18.4 |
||||
Landing | 17.8 | 18.0 |
18.3 |
18.5 |
||||
Lounge | 19.1 | 19.5 |
20.0 |
20.0 |
||||
Study | 20.0 | 20.0 |
20.0 |
20.0 |
NEEDS UPDATING
Used to get output powers using gas boiler.
Outside temperature °C | -5 | -2 | 2 | 7 | 10 | 15 |
Dining room | 810 | 452 |
||||
Lounge | 1997 | 1239 |
||||
Back Room | 889 | 500 |
||||
Front Bedroom | 607 | 179 |
||||
Back Bedroom | 622 | 191 |
||||
Study | 335 | 182 |
||||
Bathroom | 149 | 88 |
||||
Hall | 0 | 0 |
||||
Total |
5408 | 2832 |
Outside temperature °C | -5 | -2 | 2 | 7 | 10 | 15 |
Back Bedroom | 17.9 | 18.0 |
||||
Back Room | 19.9 | 20.0 |
||||
Bathroom | 20.0 | 20.0 |
||||
Dining Room | 20.0 | 20.0 |
||||
Front Bedroom | 17.9 | 18.0 |
||||
Hall | 18.1 | 18.8 |
||||
Inner Hall | 18.7 | 19.1 |
||||
Kitchen | 18.0 | 18.7 |
||||
Landing | 18.2 | 18.6 |
||||
Lounge | 19.9 | 19.9 |
||||
Study | 19.9 | 20.0 |
At 7°C outside temperature, the required heating output is the same as when using heat pumps (as it should be). However, the gas boiler is only about 55% efficient, so to get 2832W output it would need 2832/0.55 = 5149W input. Total input energy for the winter would be 5.149*24*90 = 11122kWh, which at 7.5p/kWh would cost 11122*7.5/100 = £834. This compares with £935 using A2A heat pumps.
If we had an 80% efficient boiler we would need a power input of 2832/0.8 = 3540W. Total input energy for the winter would be 3.450*24*90 = 7452kWh, which at 7.5p/kWh would cost 7452*7.5/100 = £559.
Mode | Input power W | Noise dbA |
---|---|---|
Standby | 0.6 | - |
Fan low | 7 | 38 |
Fan medium | 11 | 44 |
Fan high | 15 | 47 |
Cooling idle | 30 | 41 |
Cooling modulating | 200..740 | 45..51 |
When mounted via the plasterboard onto the wood frame below the lounge side window, vibration at about 10Hz can be felt in both the plasterboard and the window. Rumbling can also be felt/heard in the lounge, and also in the hall and study. This often hits room air resonances resulting in a "throbbing" at 2-3Hz.
Henrik settings are from DETECTING ENVIRONMENTAL NOISE WITH BASIC TOOLS.
Setting | Default | Henrik |
---|---|---|
Sampling rate | 48000 | 11025 |
FFT size | 512 | 4096 |
Decimations | 5 (=2.9Hz/bin) | 0 (=2.7Hz/bin) |
Window function | Blackman-Harris | Blackman-Harris |
Desired transformation interval | 20mS | 100ms |
Exponential smoothing factor | 0.30 | 0.95 (=Max) |
Frequency axis scale | Logarithmic | Logarithmic |
Waterfall | 1/2 screen | Off |
Max-hold trace | On | Off |
Peak markers | 1 marker | Off |
Stay awake | Off | On |
Subtract DC | On | Off |
Test signal | Off | Off |
With a 3kW immersion element we can store at most 3x4 = 12 kWh of heat during the overnight low tariff period.
The specific heat of water is 4186 J/kg/°C, and 1kWh = 3.6 MJ, so the specific heat is 4186/3.6e6 = 0.0011628 kWh/kg/°C.
If we heat the water in the cylinder to 65°C in the low tariff period and keep to at least 45°C for the rest of the day, we will be storing (65-45)*0.0011628 = 0.023256 kWh/kg = 0.023256 kWh/l. So to store 12 kWh we would need a cylinder capacity of at least 12/0.023256 = 516l. If heated to 70°C overnight and maintained to 40°C, we would need 12/(70-40)/0.0011628 = 344l, which is still huge.
With a more realistic cylinder size of 200 l and a temperature range of 20°C, we could store 20*0.0011628*200 = 4.7 kWh. With an outside temperature of 7°C, this would provide heating for 4700/837 = 5.6 hours. So we could get 5.6+4 = 9.6 hours heating at low tariff and the remaining 24-9.6 = 14.4 hours at high tariff, if we assume that no DHW is needed.
Name | Price £ inc VAT | Capacity l | ErP rating | Standing loss W | Heat-up time min | Number of immersions | Height mm | Width mm | Diameter mm |
---|---|---|---|---|---|---|---|---|---|
Telford TSMI125H | 732 | 125 | C | 62 | 36 | 1 |
610 | 935 | 510 |
Telford TSMI150H | 743 | 150 | C | 72 | 37 | 1 |
610 | 1060 | 510 |
Telford TSMI170H | 775 | 170 | C | 81 | 36 | 1 |
610 | 1200 | 510 |
Telford TSMI200H | 825 | 200 | C | 85 | 33 | 1 |
655 | 1120 | 554 |
Telford TSMI250H | 840 | 250 | C | 90 | 35 | 1 |
655 | 1130 | 554 |
Telford TSMI300H | 910 | 300 | C | 97 | 40 | 1 |
655 | 1650 | 554 |
Kingspan AUIH180ERP | 700 | 180 | C | 72 | 33 | 1 | 680 | 1258 | 550 |
Kingspan AUIH210ERP | 760 | 210 | C | 76 | 35 | 1 | 680 | 1446 | 550 |
Kingspan AUIH250ERP | 855 | 250 | C | 88 | 41 | 2 | 680 | 1696 | 550 |
Kingspan AUIH300ERP | 910 | 300 | C | 88 | 52 | 2 | 680 | 2009 | 550 |
Gledhill IND180 | 884 | 180 | C | 78 | 27 | 1 | 585 | 1306 | 550 |
Gledhill IND210 | 996 | 210 | C | 82 | 27 | 1 | 585 | 1494 | 550 |
Gledhill IND250 | 1067 | 250 | C | 86 | 36 | 2 | 585 | 1744 | 550 |
Gledhill IND300 | 1225 | 300 | C | 91 | 32 | 2 | 585 | 1990 | 550 |
Gledhill 180 Sol | 1025 | 180 | C | 78 | 21 | 1 | 585 | 1306 | 550 |
Gledhill 210 Sol | 1123 | 210 | C | 82 | 24 | 1 | 585 | 1494 | 550 |
Gledhill 250 Sol | 1220 | 250 | C | 86 | 38 | 1 | 585 | 1744 | 550 |
Gledhill 300 Sol | 1505 | 300 | C | 91 | 26 | 1 | 585 | 1990 | 550 |
Joule TCIMHI-0150LFB | 148 | ||||||||
Joule TCIMHI-0170LFC | 970 | 168 | |||||||
Joule TCIMHI-0200NFC | 1075 | 200 | C | 89 | 31 | 2 | 1085 | 600 | |
Joule TCIMHI-0250NFC | 1288 | 246 | |||||||
Joule TCIMHI-0300NFC | 1315 | 290 |
The landing cupboard is 2.4m wide, so we have 1.2m available width to the middle of the doors. This seems to preclude all but the Telford cylinders. The Telford cylinders also have the advantage that no pipes attach at the ends (this is also true of Kingspan cylinders, but they do have the immersion cap at the end).
I suspect that all horizontal cylinders have poor heat distribution when heated from the immersion, so much (or most) of the coil will probably be in cooler water. They probably don't have have such a well defined thermocline as vertical cylinders (i.e. no clear separation between hot water above and colder water below), so not so good for storing hot water when some has been used.
So forget about horizontal cylinders!
Name | Price £ inc VAT | Capacity l | ErP rating | Standing loss W | Heat-up time min | Number of immersions | Height mm | Diameter mm |
---|---|---|---|---|---|---|---|---|
Telford TSMI125H | 732 | 125 | C | 62 | 36 | 1 |
1200 | 510 |
Telford TSMI150H | 743 | 150 | C | 72 | 37 | 1 |
1120 | 580 |
These cylinders will not fit in the landing cupboard without removing the block wall to the left of the cupboard doors. They only need about 90mm extra cupboard depth, so simply replacing the block wall with plasterboard would provide most of the extra space.
The cylinders have 2 coils. The lower one is a renewable coil with 3.3m² surface area, so could be used with an A2W heat pump if we ever found a suitable one.The upper coil is a standard one, intended for use with a pumped supply from a boiler. This appears to extend from about half-way down the cylinder almost to the top, and so would sit in the hot-water part of the cylinder and be well positioned for feeding radiators.
The immersion heater is almost half-way up the cylinder, so would quickly heat only just over half of the cylinder. The rest should eventually heat up via conduction, hopefully within the 4 hour low-tariff period.
Ideally I would wire the immersion with 3 alternative routes to turn it on:
The simplest installation would be to have the immersion on all the time (with a setpoint of around 65°C).
An intermediate version would use 1 and 2, and use larger radiators in the bedrooms and study to compensate for the lower temperature. A setpoint of 45°C would probably result in a flow temperature of about 40°C, and an average radiator temperature of 35°C - so probably very big radiators.
The ideal installation would probably result in a flow temperature of about 60°C, and an average radiator temperature of 55°C.
The ideal and intermediate installations would both require the timer to be moved to the landing.
In all installation versions a room thermostat would be needed to control the radiator circulation pump.
A bypass valve might be needed to provide a circuit for the pump if all TRVs are closed, or I could simply remove the TRV from the towel rail in the bathroom. Since the pump can be run in constant-pressure mode (and we wouldn't have a boiler to be kept happy) I'm not sure we need any form of bypass. See this article about setting up the pump.
Name | Price £ inc VAT | Capacity l | ErP rating | Standing loss W | Heat-up time min | Number of immersions | Height mm | Diameter mm |
---|---|---|---|---|---|---|---|---|
Telford TSMD125 | 529 | 125 | B | 50 | 36 | 2 |
935 | 510 |
Telford TSMI150H | 545 | 150 | B | 55 | 37 | 2 |
1060 | 510 |
These are only relevant if we don't want to heat radiators from the immersion heater, and don't want to use the boiler to heat DHW.
They come with two fitted immersion heaters, both 3kW. The lower one has a "smart" thermostat (explained in the installation instructions). We would probably use this in non-smart ("OPK") mode off a timer to come on during the overnight low-tariff period, with a setpoint of about 65°C. We would probably leave the upper one on permanently with a setpoint of about 45°C, so we always have hot water available.
The immersions would have to be on separate electrical supplies - fortunately we have two radial circuits (L3 and L4) available in the landing cupboard. L4 is currently used for the immersion heater. L3 is currently used for the water pump, boiler, GCH timer and 13A socket in the lounge by the bookcase. I would have to remove the lounge socket if we wanted to use L3 for the immersion heater. I suppose I might get away with "diversity" and just use L4: if the lower immersion is on, the water should be hot enough higher up to turn off the upper immersion - however, this would involve moving the timer to the landing.
Household quotes estimates 3 to 4 hours at £30 to £60 per hour to replace an unvented cylinder. They estimate £450 (two plumbers for a day) for replacing a vented cylinder with an unvented, excluding the cost of the cylinder itself, but including labour, fittings and sundries. This is presumably at £30 per hour, so we may have to pay £900 (at £60 per hour) making the total cost around 900+760 to 900+1075 = £1660 to £1975 for a 200l cylinder.
This government survey found an average consumption for DHW of 16.8 MJ/day = 16.8*0.277778*365 = 1700 kWh/year.
According to GreenAge, average gas (hence heating+DHW) is about 12400 kWh/year.
So DHW accounts for about 1700/12400*100 = 14% of energy usage.
If heating was done by heat pumps and the DHW by immersion heater at full rate, the heating energy would be reduced to around (12400-1700)/3 = 3567 kWh/year and the proportion for DHW would increase to 1700/(3567+1700) = 32% of the total.
If all the DHW could be heated at off-peak rate, the DHW proportion would be back to around 14% in terms of cost.
Under our current Go tariff, peak rate is 15.59 p/kWh and the off-peak rate is 5 p/kWh (32% of peak rate). Average rate is (15.59*20+5/4)/24 = 13.04 p/kWh (84% of peak rate).
From July the peak rate will be 34.86 p/kWh and the off-peak rate will be 7.5 p/kWh (22% of peak rate). Average rate will be (34.86*20+7.5*4)/24 = 30.3 p/kWh (87% of peak rate).
Room | Heat loss @ -5°C | Radiator sizes | Radiator output at 70°C | Radiator output at 55°C | Radiator output at 52°C |
---|---|---|---|---|---|
Lounge | 1733 | P+ 600x600 | 1616 | 1016 | 907 |
Dining area | 838 | P+ 600x600 | 1616 | 1016 | 907 |
Back room | 967 | K1 600x900 | 882 | 555 | 495 |
Front bedroom | 454 | K1 400x700 | 470 | 296 | 264 |
Back bedroom | 479 | K1 400x700 | 470 | 296 | 264 |
Hall | 645 | P+ 500x700 | 821 | 516 | 461 |
Study | 344 | K1 600x400 | 392 | 247 | 220 |
Bathroom | 162 | Towel 1200x600 | 415 | 261 | 233 |
The theoretical maximum COP for a heat pump is given by Carnot's equation:
COPmax = Thigh / (Thigh - Tlow)
where Thigh and Tlow are the temperatures on either side of the heat pump's refrigerant circuit, measured in K.
Some examples:
Thigh °C | COPmax @ Tlow = 7 °C | COPmax @ Tlow = 0 °C |
COPmax @ Tlow = -5 °C |
---|---|---|---|
21 | 21.0 | 14.0 |
11.3 |
35 |
11.0 |
8.8 |
7.7 |
45 |
8.4 |
7.1 |
6.4 |
55 |
6.8 |
6.0 |
5.5 |
I'm hoping that actual heat pumps will approximate:
COP = E x Thigh / (Thigh - Tlow)
where E is a constant efficiency relative to the theoretical limit. E will be different for different heat pumps.
Air-to-water heat pump COPs are usually specified at 35°C and 55°C flow temperature with an outside temperature of 7°C. According to my table above, the ratio of these two COPs should be 11.0/6.8 = 1.61.
For Daikin air-to-water heat pumps, the COP ratio is in the range 1.3 to 1.4, with E values from 0.44 to 0.54.
For LG the ratio is 1.8, with E values of 0.46 and 0.41. LG also provide a COP for 2°C outside 35°C, with E of 0.40.
The COP of the Electriq isn't specified, but if we divide the heating output power power by the electrical input power we get 2930/815 = 3.60. If we assume that this is at 7°C outside and 20°C inside, we get an E value of 3.6*(20-7)/(273+20) = 0.16. If we also assume that the 2.93 kW heat output is at 7/20°C, we get the following for outputs at different outside temperatures:
Outside temperature °C | COP | Maximum output kW |
---|---|---|
-5 | 1.9 | 1.5 |
-2 | 2.1 | 1.7 |
0 | 2.3 | 1.9 |
2 | 2.6 | 2.1 |
5 | 3.1 | 2.5 |
7 | 3.6 | 2.93 |
10 | 4.7 | 3.8 |
15 | 9.4 | 7.6 |
According to my model, we need about 210W/°C to heat the house (assuming heating in the downstairs rooms only).
11 Dec 2022:
With an outside temperature of -4°C, 3 heat pumps are only managing to get the downstairs rooms to 16.5°C - i.e. temperature difference of 20.5°C. This suggests that the total heat output from the 3 heat pumps is 20.5*210 = 4305W, which is 1435W per heat pump. Average input power is about 900W (for the 2 heat pumps I am currently monitoring), so COP is about 1435/900 = 1.6. This compares with a predicted COP (for indoor temperature of 16.5°C and temperature difference of 20.5) of 0.16*(273+16.5)/20.5 = 2.3, and a predicted output power of 815*2.3 = 1870W per heat pump.
The E value under current conditions is 1.6*(16.5+4)/(273+16.5) = 0.11. Using this E value, the above table becomes:
Outside temperature °C | COP | Maximum output kW | Required kW |
---|---|---|---|
-5 | 1.3 | 1.1 |
1.7 |
-2 | 1.5 | 1.2 |
1.5 |
0 | 1.6 | 1.3 |
|
2 | 1.8 | 1.5 |
1.3 |
5 | 2.1 | 1.8 |
|
7 | 2.5 | 2.0 |
1.0 |
10 | 3.2 | 2.6 |
0.8 |
15 | 6.4 | 5.3 |
I've added a column for what my model predicts is the required heat output for each outside temperature. This suggests that the heat pumps require resistive heater assistance for outside temperatures below 0°C.
15 Dec 2022:
We did an experiment on 13 and 14 December: on the 13th we heated the back room using the heat pump only, and on the 14th we heated it using a resistive heater only and a schedule that attempted to reproduce the room temperatures that the heat pump had achieved. Average outside temperature was -0.1°C on the 13th and -0.3°C on the 14th. Outside temperature on the 12th was 0.9°, which may have aided the heat pump a little. Average back room temperature was 18.1°C on the 13th and 17.9°C on the 14th - so the experimental schedule worked OK. Average lounge temperature was 18.0°C on the 13th and 17.4°C on the 14th - this might have affected the results, but hopefully not by much.
Average power for the heat pump was 878W, and average power for the resistive heater was 1469W. This suggest a COP of around 1469/878 = 1.67 for the heat pump.
My model predicts that a heating output of about 993W would be needed under these test conditions, i.e. about 2/3 of the measured value.